Product details
Product Overview
The MC07B 0015-2B1-4-00 is a bookshelf-format inverter in the SEW-EURODRIVE MOVITRAC® B range.
It takes a single-phase 200–240 V supply and outputs 1.5 kW / 7.3 A to a three-phase motor.
CANopen is built in, so fieldbus connectivity needs no extra card.
Select U/f or sensorless vector (VFC) to match fans, pumps, or conveyors.
Cold-plate design plus forced-air cooling keep the size-0L footprint slim.
Technical Specifications
- Brand: SEW-EURODRIVE
- Model: MC07B 0015-2B1-4-00 (part no. 828 497 0)
- Series: MOVITRAC® B Standard Inverter, size 0L
- Device Type: Bookshelf cabinet inverter, single-phase input
- Electrical Data
- Supply: 1×AC 200–240 V, 50/60 Hz ±5%
- Rated motor power: 1.5 kW
- Rated output current: 7.3 A
- Output voltage: 3× 0 – Vline
- Overload: 125% IN continuous; 150% IN for min 60 s
- Max output frequency: 599 Hz
- DC bus: max permitted DC 485 V
- Integrated brake chopper (4Q); min braking resistance: 27 Ω
- Power loss: 90 W at 100% rated load
- Control modes: U/f, VFC (sensorless vector)
- I/O & Communication
- Built-in fieldbus: CANopen (integrated on base unit)
- Digital I/O: 6 programmable inputs, 2 programmable outputs, 1 relay output
- Analog: 1 setpoint input; removable signal terminals
- Option slots: DFE32B (PROFINET), DFE33B (Modbus TCP/EtherNet/IP), DFE24B/FSE24B (EtherCAT), DFP21B (PROFIBUS), DFD11B (DeviceNet), FSC11B/12B (SBus/RS485)
- Safety note: STO not supported on single-phase 230 V units
- Environmental & Mechanical
- Operating temperature: –10 to +50 °C; derate 2.5% IN/K (40–50 °C), 3% IN/K (50–60 °C)
- Storage temperature: –25 to +75 °C
- Climate class: EN 60721-3-3 class 3K3
- Protection: IP20
- Dimensions (H×W×D): 273.5 × 80 × 163.5 mm
- Weight: 2.2 kg
Installation Guide
- Mount vertically on a panel or DIN rail inside an enclosed cabinet.
- Keep 50 mm clear above and below for forced-air cooling.
- Wire the single-phase supply to L1/L2/N as shown in the manual.
- Use the removable signal terminals for quick control wiring.
- Add a braking resistor of at least 27 Ω for regenerative loads.
- Bond the cold plate to a metal surface to improve heat dissipation.
Commissioning & Maintenance
- Enter motor nameplate data and pick U/f or VFC via the keypad.
- Run auto-tune once to get the best from sensorless vector mode.
- Assign the six digital inputs to match your machine sequence.
- Monitor and debug over CANopen without opening the cabinet.
- Clean the air channels and inspect the fan every six months.
- Only the cooling fan counts as a scheduled replacement part.
Compatibility Notes
- Drives standard three-phase asynchronous and synchronous motors.
- CANopen onboard; add DFE32B/DFE33B/DFE24B for Ethernet networks.
- DFP21B and DFD11B add PROFIBUS DPV1 and DeviceNet respectively.
- DFS11B/DFS21B safety modules exist but do not apply to this unit.
- FSC11B/FSC12B add SBus and RS485 for legacy controllers.
Certifications & Standards
- EMC: integrated filter per EN 61800-3.
- Ingress protection: EN 60529, IP20.
- Climate: EN 60721-3-3 class 3K3.
- Fieldbus: CANopen CiA 402 drive profile (built in).
What’s in the Box
- 1× MC07B 0015-2B1-4-00 inverter drive (size 0L)
- 1× Removable signal terminal block
- 1× Printed installation and quick-start guide
Frequently Asked Questions
- Q: How does this differ from the 1.1 kW MC07B model?
- A: It outputs 7.3 A instead of 5.7 A and handles 1.5 kW motors. The frame and dimensions are identical.
- Q: Can I run a 2.2 kW motor at reduced load with it?
- A: No. The 7.3 A current limit will trip on a 2.2 kW motor even at light load. Choose the next size.
- Q: Why is power loss 90 W here versus 70 W on the 1.1 kW unit?
- A: The larger power stage switches more current, so it dissipates more heat. Size your cabinet ventilation accordingly.
- Q: Can I reuse the same braking resistor as the 1.1 kW model?
- A: Yes. Both share the same 27 Ω minimum and integrated chopper rating.
- Q: Does it share the same cutout as the smaller 1.1 kW version?
- A: Yes. Both are size 0L with identical 273.5 × 80 × 163.5 mm dimensions.
- Q: What wire gauge do I need for the 7.3 A output?
- A: Use 1.5 mm² (16 AWG) minimum for motor and line leads. Up-size for long cable runs.
- Q: Can it run from a diesel generator supply?
- A: Yes, if the generator is rated at least three times the drive input kVA and voltage stays within ±5%.
















There are no reviews yet.