Product details
ATV930U55N4Z at a Glance
Meet the ATV930U55N4Z from Schneider Electric. This drive belongs to the Altivar Process ATV930 family. It runs on 380…480 V three-phase power. Moreover, it carries a dual ND/HD rating. In addition, it comes in a cabinet integration version. Therefore, panel builders save space. Furthermore, a built-in brake unit removes extra parts. Besides, the IP20 frame fits tight enclosures well.
- Brand: Schneider Electric
- Model: ATV930U55N4Z
- Series: Altivar Process ATV930
- Type: Cabinet integration drive, IP20
- Supply: 380…480 V three-phase, 50/60 Hz
- Motor power (ND): 5.5 kW (7.5 HP), 120% overload for 60 s
- Motor power (HD): 4 kW (5 HP), 150% overload for 60 s
- Brake chopper: Built in, external resistor needed (min. 23 Ω)
- Safety: STO function, SIL3 / PL e
- Ports: EtherNet/IP, Modbus TCP, Modbus RTU
Motor Control and Speed
- Asynchronous motor
- Constant torque mode
- Variable torque mode
- Optimized torque mode
- Open-loop sensorless flux vector
- Closed-loop with encoder
- Synchronous PM motor
- Open-loop vector control
- Closed-loop vector control
- Synchronous reluctance motor
- Open-loop vector control
- Closed-loop vector control
- Output frequency
- 0.1…599 Hz
- Switching frequency
- 4 kHz nominal (U07N4…D45N4 frame)
- Automatic derating above nominal
Electrical Ratings
- ND Normal Duty
- Max input current: 10.4 A at 380 V
- Max input current: 9.1 A at 480 V
- Apparent power: 7.6 kVA at 380 V
- Max continuous output current: 12.7 A
- Max transient output: 15.2 A for 60 s
- HD Heavy Duty
- Max input current: 8.0 A at 380 V
- Max input current: 7.2 A at 480 V
- Apparent power: 6.0 kVA at 380 V
- Max continuous output current: 9.3 A
- Max transient output: 14.0 A for 60 s
- Short-circuit rating
- SCCR: 50 kA max
- EMC filter
- Category C2 built in
I/O and Connectivity
- Analog inputs
- 3 total
- 2 configurable 0…10 V or 0/4-20 mA
- Probe input: PTC, PT100, PT1000, KTY84
- 1 configurable 0…±10 V
- Digital inputs
- 8 inputs
- 24 V DC
- Positive or negative logic
- Digital output
- 1 assignable
- Pulse Train Output (PTO) mode
- Analog outputs
- 2 outputs
- 0…10 V or 0/4-20 mA
- Relay outputs
- 3 total: 1 NO/NC + 2 NO
- Safety inputs
- 2 inputs for STO
- Expansion
- Up to 3 I/O modules
- Analog in, digital in, relay out
- Built-in ports
- Dual-port Ethernet switch (RJ45)
- Modbus serial port (RJ45)
- Fieldbus option slot
- PROFINET
- PROFIBUS DP V1
- CANopen
- DeviceNet
- EtherCAT
- POWERLINK
Environment and Physical Data
- Operating temperature
- 0 to +40 °C standard
- Derating from 40 to 50 °C
- Storage temperature
- -40 to +70 °C
- Humidity
- 5 to 95% non-condensing
- Environmental class
- IEC 60721-3-3 class 3C3 / 3S3 / 3M3
- Altitude
- Up to 1000 m: no derating
- Above 1000 m: derate 1% per 100 m
- Protection rating
- IP20 (bottom power terminals IP00)
- Power dissipation
- 200 W (ND) at nominal load
- 137 W (HD) at nominal load
- Air flow
- Minimum 38 m³/h
- Dimensions (H×W×D)
- 285 × 130 × 196 mm
- Weight
- Not published by manufacturer
Installation Notes
- Mount the drive inside a panel. The IP20 rating therefore suits cabinet use.
- Keep 100 mm clearance above and below.
- Keep 10 mm clearance in front.
- Tighten power terminals to 2.5 N·m.
- Fit an external resistor of at least 23 Ω for braking.
- Provide at least 38 m³/h of air flow. Otherwise, heat builds up.
Best Fit Applications
- Pumps and fans in building services
- Conveyors and handling lines
- Mixers and agitators
- Packaging machines
- Textile and woodworking machines
- Small cranes and hoists
- HVAC panels and water treatment skids
Certifications
- UL 508C, UL 61800-5-1
- EN/IEC 61800-3 (C2/C3)
- EN/IEC 61800-5-1
- IEC 61508 (SIL3)
- IEC 13849-1 (Cat. PL e)
- Achilles Level 2
- REACH, SEMI F47-0706
Frequently Asked Questions
- Q: Which panel depth suits this drive?
A: The unit is 196 mm deep. Add wiring space, so a 300 mm deep cabinet works well. - Q: Can I run two motors on one drive?
A: Yes, in open-loop mode. However, each motor then needs its own overload protection. - Q: Why does my drive trip on overvoltage during braking?
A: The resistor may be too small or missing. Check the 23 Ω minimum and the wiring. - Q: How do I cut fan noise in a quiet room?
A: Lower the switching frequency. Also use the sleep function for light loads. - Q: What is the most common wiring error?
A: Swapping the STO terminals. Always verify the safety loop before the first start.















There are no reviews yet.