Product details
ATV930U75N4Z — Schneider Electric Altivar Process 7.5 kW Cabinet Drive
The ATV930U75N4Z is a three-phase variable speed drive from Schneider Electric. It belongs to the Altivar Process ATV930 series. This is the cabinet integration version. It fits inside a control panel. The unit delivers 7.5 kW in normal duty and 5.5 kW in heavy duty. It runs on 380 to 480 V supply. The protection rating is IP20, with IP00 bottom power terminals. A brake chopper is built in, so you only add an external braking resistor. This drive suits small pumps, fans, and machine builders who build their own panels.
Technical Data
- Brand: Schneider Electric
- Model: ATV930U75N4Z
- Series: Altivar Process ATV930
- Type: Three-phase variable speed drive, cabinet integration version, built-in braking unit
- Normal duty power: 7.5 kW (10 HP)
- Heavy duty power: 5.5 kW (7.5 HP)
- Overload: 120% for 60 s (ND), 150% for 60 s (HD)
Electrical Data
- Supply: 380 to 480 V three-phase, -15%/+10%, 50/60 Hz
- Output frequency: 0.1 to 599 Hz
- Switching frequency: 4 kHz nominal for this size, auto derating above this
- ND output current: 16.5 A continuous, 19.8 A for 60 s
- HD output current: 12.7 A continuous, 19.1 A for 60 s
- ND input current: 13.8 A at 380 V, 11.9 A at 480 V
- HD input current: 10.5 A at 380 V, 9.2 A at 480 V
- Apparent power: 9.9 kVA (ND) / 7.6 kVA (HD) at 380 V
- Short-circuit rating: 50 kA SCCR
- EMC filter: Category C2 integrated
Motor Control and Safety
- Motor types: Async, PM, and synchronous reluctance motors
- Control modes: Open-loop vector and closed-loop with encoder
- Safety: STO function, SIL3 / Cat. PL e
- Braking: Built-in chopper, external resistor required
- Minimum brake resistor: 19 Ω
I/O and Communication
- Analog inputs: 3 (2 voltage/current with probe input, 1 bipolar)
- Digital inputs: 8, 24 V DC, positive or negative logic
- Digital output: 1, pulse train capable
- Analog outputs: 2, voltage or current
- Relay outputs: 3 (1 NO/NC + 2 NO)
- Safety inputs: 2 for STO
- I/O expansion: Up to 3 extra modules (analog in, digital in, relay out)
- Built-in ports: 1 Ethernet dual-port switch (RJ45), 1 Modbus serial port (RJ45)
- Protocols: EtherNet/IP, Modbus TCP, Modbus RTU
- Fieldbus slot: PROFINET, PROFIBUS DP V1, CANopen, DeviceNet, EtherCAT, POWERLINK
- Cybersecurity: Achilles Level 2
Environment and Housing
- Operating temperature: 0 to +40 °C standard, derating from 40 to 50 °C
- Storage temperature: -40 to +70 °C
- Humidity: 5 to 95%, non-condensing
- Altitude: No derating to 1000 m, then 1% per 100 m to 3000 m
- Environmental class: 3C3 / 3S3 / 3M3
- Protection: IP20, bottom power terminals IP00
- Dimensions (H x W x D): 345 x 155 x 225 mm
- Weight: Not published by the manufacturer
- Power loss: 259 W (ND) / 193 W (HD) at nominal load
- Minimum air flow: 103 m³/h
Installation Notes
- Mount the drive inside a panel or cabinet.
- Keep 100 mm free space above and below.
- Keep 10 mm free space at the front.
- Tighten power terminals to 2.5 N·m.
- Add an external braking resistor, 19 Ω minimum.
- Plan for airflow of 103 m³/h.
- Watch the IP00 bottom terminals inside the panel.
Setup and Service
- Enter motor data with the keypad or software.
- Select ND or HD mode to match the load.
- Use the dual Ethernet port for simple wiring.
- Clean heat sinks and check fans on schedule.
- Read fault codes on the display for fast repair.
Compatibility
- Handles async, PM, and synchronous reluctance motors.
- Supports encoder feedback for closed-loop control.
- Joins PROFINET, EtherCAT, CANopen, and other networks with one option module.
- Accepts up to 3 extra I/O modules.
- Works with external braking resistors from 19 Ω.
- Connects to plant systems through EtherNet/IP and Modbus TCP.
Certifications
- UL 508C and UL 61800-5-1
- EN/IEC 61800-3 (category C2/C3)
- EN/IEC 61800-5-1
- IEC 61508 and ISO 13849-1 for STO
- Achilles Level 2
- REACH and SEMI F47-0706
Package Contents
- 1 x ATV930U75N4Z drive
- 1 x printed installation manual
- 1 x safety information sheet
- Terminal hardware as shipped by Schneider Electric
Best Fit Applications
- Panel builders and machine OEMs
- Small water and booster pumps
- Compact HVAC fans
- Packaging and labeling machines
- Material handling equipment
- Retrofit projects inside existing cabinets
FAQ
- Why choose the Z version instead of a wall-mount unit?
This model fits inside a panel. It saves space and shares the cabinet’s cooling and protection. - What resistor value do I need?
Use a resistor of at least 19 Ω. The chopper is already inside the drive. - What is the top ambient temperature?
It runs at full rating to 40 °C. Above that, the output current must drop up to 50 °C. - How do panel builders handle the IP00 terminals?
They cover the bottom terminals or place the drive behind a barrier inside the enclosure. - What do commissioning teams do before the first run?
They check terminal torque, set motor data, and test the STO circuit.















There are no reviews yet.