Product details
ATV930U40N4Z – Compact Power for Your Panel
The ATV930U40N4Z is a three-phase drive from Schneider Electric. It belongs to the Altivar Process ATV930 series. This version fits inside a cabinet. It runs on 380…480 V and gives 4 kW in Normal Duty. Moreover, it has a built-in braking unit. So the panel stays small and wiring stays short.
Spec Tree at a Glance
- Hardware
- Normal Duty: 4 kW (5 HP), 120% for 60 s
- Heavy Duty: 3 kW, 150% for 60 s
- Switching rate: 4 kHz nominal
- Output range: 0.1…599 Hz
- Motor types: async, PM sync, sync reluctance
- Safety: STO, SIL3 / Cat. PL e
- Brake: built-in chopper; resistor 34 Ω min
- I/O
- Analog in: 3 ports (voltage, current, probe)
- Digital in: 8 ports, 24 V DC
- Digital out: 1 port, pulse train ready
- Analog out: 2 ports
- Relay out: 3 ports (1 NO/NC + 2 NO)
- STO in: 2 ports
- Expansion: up to 3 extra modules
- Comms
- Ports: Ethernet dual switch + Modbus serial
- Protocols: EtherNet/IP, Modbus TCP, Modbus RTU
- Option slot: PROFINET, PROFIBUS, CANopen, DeviceNet, EtherCAT, POWERLINK
- Security: Achilles Level 2
- Power
- Input: 380…480 V, -15%/+10%, 50/60 Hz
- ND current: 7.6 A at 380 V; 6.7 A at 480 V
- ND output: 9.3 A steady; 11.2 A for 60 s
- HD current: 6.0 A at 380 V; 5.4 A at 480 V
- HD output: 7.2 A steady; 10.8 A for 60 s
- SCCR: 50 kA
- EMC: C2 filter built in
- Environment
- Class: 3C3 / 3S3 / 3M3 (except frame 7)
- Certs: UL 508C, UL61800-5-1, IEC 61800-3, IEC 61508, IEC 13849-1, Achilles L2, REACH, SEMI F47
- Altitude: no derate to 1000 m; then 1% per 100 m
- Temp: 0 to +40 °C; derate to 50 °C
- Storage: -40 to +70 °C
- Humidity: 5…95%, no condensation
- Rating: IP20 (bottom power terminals IP00)
- Physical
- Heat loss: 142 W (ND) / 108 W (HD)
- Air flow: 38 m³/h min
- Size: 285 x 130 x 196 mm
- Torque: 2.5 N·m power terminals
- Clearance: 100 mm top/bottom, 10 mm front
Where It Shines
This drive fits small pumps, fans, and conveyors. It also works well in packaging lines and machine tools. Because it mounts inside a panel, it keeps your cabinet neat. In addition, the STO input adds safety with little wiring.
Good Match for These Devices
- Small async motors up to 4 kW
- PM sync motors with or without encoder
- Sync reluctance motors
- Panels using EtherNet/IP or Modbus
- Machines that must meet SIL3 rules
FAQ
- Q: Why does the HD power value show a dash?
A: Schneider does not publish a heavy duty kW for this size. In practice, use the HD current of 7.2 A as your guide. - Q: Can I put this unit in a sealed panel?
A: Yes, but you must move at least 38 m³/h of air. Add a fan or vent, or the drive will run hot. - Q: How is this model different from a wall-mount drive?
A: It has no keypad on the front and sits flush in a panel. Wires go to the bottom terminals, which sit at IP00. - Q: Does the drive need a line reactor?
A: Not always. The C2 filter handles most noise. Still, check your site rules and cable length before you skip it. - Q: What is the smallest brake resistor I can use?
A: 34 Ω. Going lower may damage the chopper. Always check the duty cycle of your load first.















There are no reviews yet.