Product details
ATV610D90N4Z: Big Power for Pumps and Fans
The ATV610D90N4Z is a heavy-duty variable speed drive from Schneider Electric. It sits in the Easy Altivar 610 series. This model rates 90 kW (125 HP) normal duty on a 380…460 V three-phase supply. A category C3 EMC filter is built in. The unit ships without a plain text display terminal. You can add the VW3A1113 keypad through the HMI RJ45 port. It uses frame size 5 and a fan that swaps in under 5 minutes. In short, it is made to move air and water at high power.
Where It Fits Best
- Pumping systems
- Booster and transfer pumps
- Irrigation and water supply
- Waste water lift stations
- Air systems
- Supply and return fans
- Cooling tower fans
- Large air handling units
- Process plant
- HVAC plant rooms
- Industrial ventilation
- Light mixers and agitators
Hardware Tree
- Motor types
- Three-phase asynchronous motors
- Synchronous PM motors, open loop
- Reluctance motors (SRVC)
- Control methods
- STD: U/f Vc Standard
- UF5: U/f Vc 5-point
- UFQ: U/f Vc Quadratic for fans and pumps
- SYNU: open loop for PMSM
- SRVC: reluctance motor control
- Power ratings
- Normal duty: 90 kW (125 HP)
- Heavy duty: 75 kW (100 HP)
- Frame size: 5
- Interface
- No keypad in the box
- VW3A1113 keypad plugs into the HMI RJ45 port
- Plain text display is optional
- Wiring and service
- Power terminals tighten to 25 N·m
- Fan replaces in under 5 minutes
- No special tools needed
I/O Tree
- Analog inputs
- 3 ports
- Set by software to 0…10 V or 0…20 mA
- Accepts voltage, current, temperature probe, or water level
- Digital inputs
- 6 ports at 24 V DC
- 2 can work as pulse inputs
- Analog outputs
- 2 ports
- Set by software to 0…10 V or 0…20 mA
- Relay outputs
- 3 relays with configurable logic
- Slot A options
- Extended I/O module VW3A3203
- Extended relay module VW3A3204
Communication Tree
- Two built-in RJ45 Modbus ports
- Field network port
- Bottom of the control block
- Moves process data over Modbus serial link
- Shown as [Modbus network diag] MND
- HMI port
- Front of the control block
- For VW3A1113 keypad
- Also for Harmony or Magelis HMI
- Also for a configuration loader
- Shown as [Modbus HMI Diag] MDH
- Field network port
- Protocol
- Modbus RTU on RS485
- Terminals A, B, SGND
- Slot A expansion
- PROFIBUS DP V1 module VW3A3607
- 9-way female SUB-D
- Profidrive and CiA402 profiles
Electrical Tree
- Supply
- 380…460 V AC, three-phase, 50/60 Hz
- Input current
- 177.8 A max at 380 V
- 159.9 A max at 460 V
- Values for normal duty
- Power and fault level
- Apparent power 127.4 kVA at 460 V
- SCCR up to 50 kA
- Output
- Continuous 173 A normal duty
- Transient 190 A for 60 s
- Heavy duty 145 A continuous
- Heavy duty transient 218 A for 60 s
- Frequency range 0.1…500 Hz
- Switching
- 1…8 kHz adjustable
- 2.5 kHz nominal
- Derate above nominal
- Motor cable
- 150 m shielded
- 200 m unshielded
- Add an output filter above 50 m
- Harmonics
- Built-in DC choke cuts distortion
- THDi under 10% needs passive filter VW3A46xxx
- The choke alone does not reach that level
- Overload
- Normal duty 110% for 60 s
- Normal duty 120% for 20 s
- Heavy duty 150% for 60 s
- Braking
- PA/+ and PB terminals for an external resistor
- Heat
- 1944 W inside a closed cabinet at nominal current
Environment and Housing
- Temperature
- Run -15…+45 °C with no derating
- Up to +60 °C with derating
- Store -40…+70 °C
- Humidity
- 5…95%, no condensation
- Altitude
- No derating up to 1000 m
- Derate from 1000 to 3000 m
- Protection
- IP20 body
- IP40 on top
- Classes
- 3C3 / 3S3 per IEC/EN 60721
- Mechanical class 3M3
- Conformal coating on boards
- Mounting
- Vertical, ±10°
- Clearance 100 mm top
- Clearance 100 mm bottom
- Clearance 10 mm front
- Relay supply
- Must be Overvoltage Category II (OVC II)
- Otherwise add an isolation transformer
- Size and weight
- 762 × 290 × 323 mm
- 52.045 kg without packaging
- The N4Z version is lighter than the N4 keypad version
Certifications
- CE marking under the EMC directive
- CSA C22.2 No. 274 for Canada
- No UL listing is published in the official catalog or manual
FAQ
Q: Will this unit carry a 90 kW fan at full speed all day?
A: Yes. Normal duty output is 173 A. Keep cabinet heat below the stated limit, because the drive sheds 1944 W.
Q: Can I run a 75 kW motor with heavy starts?
A: Yes. Switch to heavy duty mode. You then get 145 A continuous and 218 A for 60 s.
Q: Is a keypad needed to set the drive up?
A: Not strictly. You can load a config file through the HMI port. Most sites still add the VW3A1113 for local checks.
Q: How short is a fan swap?
A: Under 5 minutes. The fan pulls out by hand, so no special tools are needed.
Q: From field practice, what causes nuisance trips on big drives like this?
A: Weak airflow and long motor cables cause most faults. Keep 100 mm free above and below. Fit an output filter when runs pass 50 m.
Lifecycle Note
The Easy Altivar 610 line is active as of 2026-10. Schneider Electric still hosts official product pages.














There are no reviews yet.