Product details
ATV610C11N4Z: Big Power for Pumps and Fans
ATV610C11N4Z is a Schneider Electric drive for large pump and fan jobs. It runs at 110 kW (150 HP) normal duty on 380…460 V three-phase. A heavy duty rating of 90 kW is also available. The drive has an integrated C3 EMC filter. It comes without a display to keep the price low. You can add the VW3A1113 keypad later. The case is IP00. Add the IP21 kit for touch safety. Also, a built-in DC choke cuts harmonics. However, THDi under 10% needs the optional passive filter. Therefore, plan that part if power quality matters. The fan is field-replaceable in under 5 minutes.
Technical Specifications
- Brand: Schneider Electric
- Model: ATV610C11N4Z
- Series: Easy Altivar 610
- Type: Variable speed drive (AC frequency inverter) for pumps and fans
- Motor Power: 110 kW (150 HP) normal duty; 90 kW (125 HP) heavy duty
- Supply: 380…460 V three-phase, 50/60 Hz
- Input Current: 201 A at 380 V; 175.7 A at 460 V (ND)
- Output Current: 211 A continuous (ND); 173 A (HD)
- Transient Current: 232 A for 60 s (ND); 260 A (HD)
- Apparent Power: 140 kVA at 460 V
- SCCR: 50 kA
- Output Frequency: 0.1…500 Hz
- Switching Frequency: 1…8 kHz adjustable; 2.5 kHz nominal (derate above)
- Control Modes: U/f STD, U/f 5-point, U/f quadratic, open-loop PMSM, reluctance motor
- Motor Cable: 150 m shielded / 200 m unshielded; output filter advised above 50 m
- Analog Inputs: 3, configurable 0…10 V / 0…20 mA
- Digital Inputs: 6, 24 V DC (2 can be pulse inputs)
- Analog Outputs: 2, configurable 0…10 V / 0…20 mA
- Relay Outputs: 3, configurable logic
- I/O Expansion: Slot A for VW3A3203 (extended I/O) or VW3A3204 (extended relay)
- Ports: 2 RJ45 Modbus serial-link ports (field network + HMI)
- Protocol: Modbus RTU over RS485
- Expansion: Slot A for PROFIBUS DP V1 module VW3A3607
- Braking: external resistor terminals PA/+, PB
- Power Loss: 2290 W at nominal current (enclosed cabinet)
- Operating Temperature: -15…+45 °C no derating; up to +60 °C with derating
- Storage Temperature: -40…+70 °C
- Humidity: 5…95%, no condensation
- Altitude: 1000 m no derating; 1000…3000 m with derating
- Protection: IP00 (IP21 kit optional)
- Coating: conformal coated boards
- Size (H×W×D): 850 x 300 x 375 mm (frame 6)
- Weight: 85.445 kg (188.4 lb)
- Terminal Torque: 27 N·m (frame 6)
- Clearance: top 250 mm, bottom 250 mm, front 100 mm; mount vertical ±10°
Installation Guide
- Mount the drive vertical. Tilt no more than ±10°.
- Keep 250 mm free at top and bottom. Keep 100 mm in front. This keeps the fan working well.
- Tighten power terminals to 27 N·m.
- Use shielded cable up to 150 m. Add an output filter above 50 m.
- Fit the IP21 kit if people can touch the drive.
- Keep relay supply at OVC II. Use an isolation transformer if not.
- Add the external resistor on PA/+ and PB for braking.
Setup and Service
- Set switching frequency from 1 to 8 kHz. Nominal is 2.5 kHz.
- Derate power above 2.5 kHz.
- Derate load above 45 °C or 1000 m altitude.
- Plug the VW3A1113 keypad into the HMI RJ45 port for setup.
- Change the fan in under 5 minutes. No special tools needed.
- Clean the heatsink at each service visit. Dust cuts cooling.
Compatibility Notes
- Runs asynchronous motors, PMSM, and reluctance motors in open loop.
- Ships with Modbus RTU on two RJ45 ports.
- Add the VW3A3607 module for PROFIBUS DP V1. Thus it fits plant networks.
- Add the VW3A3203 or VW3A3204 in Slot A for more I/O.
- Works with the optional passive filter VW3A46xxx for THDi under 10%.
Certifications
- CE (EMC directive)
- CSA C22.2 No. 274 (Canada)
- IEC/EN 60721 class 3C3 / 3S3; mechanical class 3M3 (frames 1-6)
- IEC/EN 61800-5-1 overvoltage category II for relay supply
- UL listing: not published in the official catalog.
Package Contents
- ATV610C11N4Z drive
- Installation manual EAV64381
- Safety sheet
- Quick start guide
Best Fit: Equipment and Applications
- HVAC fans: air handling and cooling towers
- Water pumps: supply, booster, and irrigation stations
- Wastewater: aeration blowers and transfer pumps
- District energy: circulation pumps in plants
- Process cooling: large fans in dry or wet rooms
FAQ
- Q: My pump motor overheats at low speed. What should I check?
A: Fans on motors cool less at low speed. Check the motor rating for variable torque. Then set the U/f quadratic curve. If heat persists, add a forced-air fan to the motor. - Q: The drive trips on overvoltage during pump stop. Why?
A: Fluid in the pipe pushes the motor after stop. Add a 27 N·m-checked external resistor on PA/+ and PB. Or set a longer deceleration ramp. Both steps reduce the trip risk. - Q: Harmonic levels at my site are too high. Can this drive help?
A: The built-in DC choke lowers harmonics. But THDi under 10% needs the passive filter VW3A46xxx. Check your grid code first. Then size the filter for the load. - Q: Can I add a keypad after I buy the drive?
A: Yes. The VW3A1113 keypad plugs into the HMI RJ45 port. This N4Z version ships without a display. Add the keypad when local setup is needed. - Q: The fan makes noise after two years. Is that a problem?
A: It may be dust on the blades. Clean the fan and heatsink first. If the noise stays, swap the fan. It takes under 5 minutes and needs no special tools.