Product details
ATV610D45N4Z: Built for Moving Air and Water
Meet the ATV610D45N4Z. This Schneider Electric Easy Altivar 610 drive runs 45 kW (60 HP) pumps and fans. It takes a 380 to 460 V three-phase feed. A C3 EMC filter is inside. A DC choke trims harmonics. This version ships without a keypad. Add the VW3A1113 keypad for local control. Steady output. Low fuss. Long service life.
Identity Card
- Brand: Schneider Electric
- Model: ATV610D45N4Z
- Series: Easy Altivar 610
- Type: AC frequency inverter for variable speed control
- Frame: 4
Power Profile
- Normal duty: 45 kW / 60 HP
- Heavy duty: 37 kW / 50 HP
- Line supply: 380 to 460 V, three-phase, 50/60 Hz
- Output frequency band: 0.1 to 500 Hz
- Carrier frequency: 2 to 12 kHz, nominal 4 kHz
- Normal duty current: 88 A steady, 97 A peak for 60 s
- Heavy duty current: 74.5 A steady, 112 A peak for 60 s
- Overload window: 110% for 60 s or 120% for 20 s
- Heavy duty overload: 150% for 60 s
- Line current: 92.9 A at 380 V, 82.7 A at 460 V
- Apparent power: 65.9 kVA at 460 V
- SCCR: 22 kA maximum
- Heat loss: 1121 W in a closed cabinet
Motor and Control Menu
- Open-loop three-phase induction motors
- Open-loop PM synchronous motors via SYNU
- Reluctance motors via SRVC
- U/f curves
- STD, the standard curve
- UF5, the 5-point curve
- UFQ, the quadratic curve for fans and pumps
Input and Output Layout
- 3 analog inputs, set in software to 0 to 10 V or 0 to 20 mA
- They read voltage, current, temperature probes or level sensors
- 6 digital inputs at 24 V DC; 2 double as pulse inputs
- 2 analog outputs, set in software
- 3 relay outputs with flexible logic
- Slot A options
- VW3A3203 extended I/O module
- VW3A3204 extended relay module
Network Tree
- Two RJ45 ports come built in
- Field network port
- Located at the bottom of the control block
- Carries process data over Modbus serial link
- Menu code MND
- HMI port
- Located at the front of the control block
- Multidrop for the VW3A1113 keypad
- Also serves Harmony or Magelis panels
- Menu code MDH
- Field network port
- Link layer
- Modbus RTU on RS485
- Wiring on A, B and SGND
- Speed, parity and function codes: see manual EAV64395
- Fieldbus option in Slot A
- PROFIBUS DP V1 module VW3A3607
- One 9-way SUB-D female socket
- Supports Profidrive and CiA402 profiles
Ruggedness and Ratings
- Runs at -15 to +45 °C with no derating
- Reaches +60 °C with power derating
- Storage span: -40 to +70 °C
- Humidity: 5 to 95%, no condensation
- Altitude: 1000 m free; derate above that
- Ingress rating: IP20, with IP40 on top
- Climate class: 3C3 / 3S3 per IEC/EN 60721
- Mechanical class 3M3
- Cards come with a conformal coating
- Relay feed needs OVC II; add an isolation transformer if not
Mounting and Upkeep
- Fit the unit upright, within ±10°.
- Leave 100 mm above and below, 10 mm in front.
- Power terminals: tighten to 12 N·m.
- Cable length: 100 m shielded, 200 m unshielded.
- Fit a dv/dt filter past 50 m.
- Fan change takes under 5 minutes, no special tools.
Approvals
- CE marking under the EMC directive
- CSA C22.2 No. 274 for Canada
- No UL listing in the official catalog
What Comes in the Box
- One ATV610D45N4Z drive
- One installation manual
- One safety leaflet
- Unit weight: 25.295 kg
- Note: keypad sold separately
Where It Shines
- Municipal water and wastewater pumps
- HVAC supply and extract fans
- Cooling tower and condenser fans
- Air handling units with variable torque loads
- Pressure booster stations
- Farm irrigation pump lines
- Factory exhaust and process ventilation
FAQ
Q: Is a display unit in the box?
A: No. Buy the VW3A1113 keypad if you want one.
Q: Which curve fits fan and pump loads best?
A: Pick UFQ, the quadratic curve. It saves energy at part speed.
Q: Can I add a fieldbus later?
A: Yes. Slot A takes the VW3A3607 PROFIBUS DP V1 card.
Q: What overload does heavy duty give me?
A: 150% of rated current for 60 s at 37 kW.
Q: Does the drive brake a load by itself?
A: No. Wire an external resistor to PA/+ and PB for braking.
Q: What trips up first-time installers?
A: Relay contact arcing. Feed the relays from an OVC II source. Add an isolation transformer when in doubt.
Q: Any advice on long cable runs?
A: Keep shielded cable at 100 m or less. Past 50 m, fit a dv/dt filter. This prevents motor winding stress.