ATV610D37N4Z: Power for Pumps and Fans

The ATV610D37N4Z is a Schneider Electric Easy Altivar 610 drive. It runs 37 kW (50 HP) pumps and fans. The 380 to 460 V three-phase supply fits most plants. A C3 EMC filter comes built in. The DC choke cuts harmonics. This unit has no keypad. Add the VW3A1113 keypad when you need local control. Simple, rugged, and ready for HVAC duty.

Quick Facts

  • Brand: Schneider Electric
  • Model: ATV610D37N4Z
  • Series: Easy Altivar 610
  • Type: Variable speed drive (AC frequency inverter)
  • Frame: 4

Core Ratings

  • Normal duty: 37 kW / 50 HP
  • Heavy duty: 30 kW / 40 HP
  • Supply: 380 to 460 V, three-phase, 50/60 Hz
  • Output frequency: 0.1 to 500 Hz
  • Switching frequency: 2 to 12 kHz, nominal 4 kHz
  • Continuous output: 74.5 A normal duty
  • Transient output: 82 A for 60 s
  • Heavy duty current: 59.6 A continuous, 89.4 A transient
  • Overload: 110% for 60 s or 120% for 20 s (normal duty)
  • Overload: 150% for 60 s (heavy duty)
  • Input current: 76.6 A at 380 V, 68.3 A at 460 V
  • Apparent power: 54.4 kVA at 460 V
  • SCCR: 22 kA maximum
  • Power loss: 951 W in a closed cabinet

Control and Motor Support

  • Open-loop asynchronous motors
  • Open-loop synchronous PM motors (SYNU)
  • Reluctance motors (SRVC)
  • U/f Standard, 5-point and Quadratic curves
  • Quadratic curve suits variable-torque fans and pumps

I/O at a Glance

  • 3 analog inputs: 0 to 10 V or 0 to 20 mA, software set
  • 6 digital inputs at 24 V DC; 2 act as pulse inputs
  • 2 analog outputs: 0 to 10 V or 0 to 20 mA
  • 3 relay outputs with configurable logic
  • Slot A takes the VW3A3203 extended I/O module
  • Slot A also takes the VW3A3204 extended relay module

Communication Tree

  • Built-in ports
    • Field network RJ45
      • Bottom of control block
      • Modbus serial link for process data
      • Diagnostic menu: MND
    • HMI RJ45
      • Front of control block
      • Multidrop for VW3A1113 keypad
      • Also links Harmony or Magelis HMI
      • Diagnostic menu: MDH
  • Protocol
    • Modbus RTU over RS485
    • Terminals A / B / SGND
    • Baud rate, parity and function codes: see Modbus manual EAV64395
  • Expansion slot A
    • PROFIBUS DP V1 module VW3A3607
    • 9-way SUB-D female port
    • Profidrive and CiA402 profiles

Environment and Protection

  • Operating range: -15 to +45 °C without derating
  • Up to +60 °C with power derating
  • Storage: -40 to +70 °C
  • Humidity: 5 to 95%, no condensation
  • Altitude: 1000 m without derating; derate above
  • Rating: IP20, IP40 on top
  • Classes: 3C3 / 3S3 per IEC/EN 60721
  • Mechanical class 3M3
  • Cards carry a conformal coating
  • Relay supply needs OVC II; else use an isolation transformer

Install and Care

  • Mount vertical, within ±10°.
  • Keep 100 mm top and bottom, 10 mm front.
  • Tighten power terminals to 12 N·m.
  • Cable run: 100 m shielded, 200 m unshielded.
  • Add a dv/dt filter above 50 m.
  • Fan swaps out in under 5 minutes, no special tools.

Certifications

  • CE marking (EMC directive)
  • CSA C22.2 No. 274 (Canada)
  • No UL listing in the official catalog

Packing List

  • One ATV610D37N4Z drive
  • One installation manual
  • One safety sheet
  • Box weight: 25.295 kg
  • Note: keypad not included

Best Fit Applications

  • Centrifugal pumps in water and waste plants
  • Supply and return fans in HVAC systems
  • Cooling tower fans
  • Air handling units
  • Booster pump sets
  • Industrial ventilation
  • Irrigation pumps

FAQ

Q: Does the box include a keypad?

A: No. Order the VW3A1113 keypad if you want local control.

Q: Can it drive a permanent magnet motor?

A: Yes. Use open-loop SYNU control for PMSM.

Q: How do I reach the network port?

A: The field RJ45 sits at the bottom of the control block.

Q: What cable run is safe?

A: Stay at 100 m or less for shielded cable.

Q: Is there a braking resistor inside?

A: No. Wire an external resistor to the PA/+ and PB terminals.

Q: What do service techs see most in the field?

A: Heat faults from tight cabinets. Leave the 100 mm gap. Clean the fan each year. Check the 12 N·m torque at every service.

Q: Any tip on harmonics?

A: The DC choke helps, but THDi under 10% needs the VW3A46 passive filter. Budget for it on weak grids.

Specifications

  • BrandAllen-Bradley
  • Part Number22A-B012F104
  • ConditionOriginal Brand New

Customers Reviews

There are no reviews yet.

Be the first to review “ATV610D37N4Z Schneider Easy Altivar 610 37 kW Pump Fan Drive”

Your email address will not be published. Required fields are marked *

Back to Top
Product has been added to your cart