ATV320U55N4W | Schneider Electric Altivar Machine ATV320 5.5 kW IP66 Drive
Here is the ATV320U55N4W. It belongs to the Altivar Machine ATV320 family from Schneider Electric. This unit drives 5.5 kW (7.5 HP) motors on 380 to 500 V three-phase power. The IP66 case is fully sealed. A category C2 EMC filter is built in. Big torque, a 599 Hz top frequency and SIL3/PLe safety come in one rugged box. It is a strong pick for mid-size machines that face dust, wet floors or outdoor use.
Name Plate
- Brand: Schneider Electric
- Model: ATV320U55N4W
- Series: Altivar Machine ATV320
- Type: Three-phase variable speed drive, wall mount, IP66
Power Core
- Motor power: 5.5 kW (7.5 HP) at 380 to 500 V three-phase
- Nominal output current: 14.3 A at 4 kHz
- Transient current: 21.5 A for 60 s (150% of In)
- Output frequency: 0.1 to 599 Hz
- Switching frequency: 2 to 16 kHz, 4 kHz preset; derate above 4 kHz
- Overload torque: up to 200% Tn over-torque and 170% Tn braking torque
- Rating: one rating only; no Normal Duty or Heavy Duty split
Line Feed
- Voltage: 380 to 500 V three-phase, -15%/+10%, 50/60 Hz
- Input current: 20.7 A at 380 V; 14.5 A at 500 V
- Apparent power: 12.6 kVA at 500 V maximum
- SCCR: 22 kA maximum
- Losses: 195 W at In and rated switching frequency
Control Brain
- Async motor: U/F ratio (2-point, 5-point, energy-saving, quadratic) and sensorless flux vector control
- PM motor: sensorless vector control
- Analog path: 10-bit resolution on the analog output
I/O Branches
- Analog inputs
- 1 x bipolar differential ±10 V
- 1 x 0 to 10 V
- 1 x 0 to 20 mA
- PTC probe support
- Digital inputs
- 4 x 24 V DC, sink/source, configurable
- 1 x PTC probe
- 1 x pulse, up to 20 kHz
- Digital output: 1 x 24 V DC sink/source, 100 mA maximum
- Analog output: 1 x 0 to 10 V or 0/4 to 20 mA, 10 bits
- Relay outputs
- 1 x NO/NC contact
- 1 x NO contact
- 3 A at 250 VAC resistive load
- Pulse output: 1 x 24 V, 32 kHz maximum, 0.1 A
- Safety inputs
- 1 x STO
- 4 x configurable for SS1, SLS, SMS and GDL
- STO reaches SIL3 and PLe
Brake Path
- Method: external dynamic braking resistor
- Minimum value: 27 Ω
- Note: fit an outside resistor for fast stops or high inertia loads
Network Branches
- Built-in port
- 1 x RJ45
- CANopen
- Modbus Serial Line
- Expansion slot
- Modbus TCP and EtherNet/IP
- PROFIBUS DP V1
- DeviceNet
- EtherCAT
- POWERLINK
- PROFINET
- Cyber certificate: none published by the maker
Weather and Noise
- Protection: IP66
- Running temperature: -10 to +50 °C with no derating; up to 60 °C with derating
- Storage temperature: -25 to +70 °C
- Humidity: 5 to 95%, no condensation, no dripping water
- Height: no derating to 1000 m; 1% current loss per 100 m up to 3000 m
- EMC: built-in C2 filter; 10 m shielded motor cable at 4 kHz (C2 and C3)
- Ambient class: IEC 60721-3-3 class 3C3/3S2
Body Size
- Dimensions (H×W×D): 521 x 320 x 335 mm
- Weight: 22.000 kg (48.501 lb)
- Terminal torque: 1.2 to 1.5 N·m (Frame 4)
- Wire size: 4 to 16 mm² (Frame 4)
Where It Shines
- Heavy conveyors and bulk handlers that need strong low-speed torque
- Pumps and fans in water, food and HVAC plants
- Mixers, agitators and extruders with hard starts
- Packaging and palletizing lines in wet or dusty rooms
- Lifting and hoisting gear that uses brake control
- Outdoor skids and washdown zones where a sealed box replaces a cabinet
Mount and Wire
- Mount upright. A tilt of ±10° is fine.
- Leave 100 mm free space on all sides.
- Tighten power screws to 1.2 to 1.5 N·m.
- Use wire from 4 to 16 mm².
- Keep shielded motor cable at or under 10 m for C2 EMC.
- Fit a resistor of at least 27 Ω for braking duty.
- Cut current 1% per 100 m above 1000 m altitude.
Commission and Care
- Set up the unit over the RJ45 port with Modbus or CANopen.
- Add the VW3A1111 or VW3A1101 terminal for local control.
- Copy settings to a spare drive to cut downtime.
- The sealed housing needs no filter swap.
- Stay at 4 kHz unless you check the derating curve.
Match and Fit
- Runs standard async motors and PM motors.
- Works on 380 to 500 V grids at 50 or 60 Hz.
- Pairs with GV2 breakers using the mounting bracket.
- Takes DIN rail plates and UL Type 1 kits.
- Adds one fieldbus module through the free slot.
Approvals
- UL 508C and UL 61800-5-1
- CSA 22.2 N274
- EN/IEC 61800-3 category C2/C3
- EN/IEC 61800-5-1
- IEC 61800-5-2 up to SIL3 and IEC 61508 SIL3
- ISO 13849-1 PLe
- IEC 60721-3-3 class 3C3/3S2
- RCM, EAC and KC
In the Box
- 1 x ATV320U55N4W drive
- 1 x printed installation manual
- 1 x safety sheet
- Terminal parts as packed by Schneider Electric
- Display terminal and brake resistor sold apart
FAQ
Is 5.5 kW enough for my pump or fan?
Usually yes for medium flow duties. Check the motor nameplate first. The drive gives 14.3 A and handles light overload for up to 60 s.
Why is the SCCR higher on this frame?
Larger frames take more fault current. This model rates 22 kA. Match your breaker or fuse to that value for safe short-circuit protection.
Do I need a line reactor?
Not always. The built-in C2 filter handles most noise. Add a reactor when the supply is weak or the cable run is very long.
How do I cool a sealed unit in a hot room?
Keep 100 mm free on all sides. Stay under 50 °C for full current. Above that, lower the load or add airflow around the case.
Can I lift a load with this drive?
Yes, with care. Use the brake control and an outside resistor of at least 27 Ω. Add a mechanical brake for holding duty.
What is a common wiring mistake?
Loose power lugs. They heat up and trip the drive. Use a torque wrench and hit 1.2 to 1.5 N·m on every terminal.