Product details
ATV320U75N4W Schneider Electric Altivar Machine ATV320 Variable Speed Drive
ATV320U75N4W is a 7.5 kW wall-mounting three-phase drive from the Altivar Machine ATV320 series by Schneider Electric. It combines an IP66 enclosure with an integrated EMC filter. The unit suits demanding machine builders who need reliable motor control in harsh plant conditions.
The drive runs asynchronous and synchronous PM motors. It offers U/F control and sensorless vector control. A single rating covers 17.0 A continuous output. Overload reaches 150% for 60 seconds. Setup is fast through the built-in RJ45 port. The port supports CANopen and Modbus Serial line.
- Core value: one compact drive for wall mounting, harsh areas, and mixed motor types
- Best fit: packaging, material handling, Textile, woodworking, and pump or fan machines
- Why it stands out: IP66 protection plus C2 EMC filter in a single unit
Technical Data
- Brand: Schneider Electric
- Model: ATV320U75N4W
- Series: Altivar Machine ATV320
- Module type: IP66 wall-mounting three-phase variable speed drive
- Motor power: 7.5 kW (10 HP) at 380 to 500 V three-phase
- Supply voltage: 380 to 500 V three-phase, -15%/+10%, 50/60 Hz
- Input current: 26.5 A max at 380 V, 18.7 A max at 500 V
- Apparent power: 16.2 kVA max at 500 V
- Short-circuit rating: SCCR up to 22 kA
- Output current: 17.0 A continuous at 4 kHz
- Transient current: 25.5 A for 60 s (150% of In)
- Overload torque: up to 200% Tn over-torque, 170% Tn braking torque in open loop
- Output frequency range: 0.1 to 599 Hz
- Switching frequency: 2 to 16 kHz programmable, factory 4 kHz
- Control modes: U/F ratio, sensorless flux vector, synchronous PM vector control
- Resolution and accuracy: 10-bit analog output resolution, stable speed holding in vector mode
- Measurement range: analog inputs cover ±10 V bipolar, 0 to 10 V, and 0 to 20 mA
- Temperature range: -10 to +50 °C without derating, up to 60 °C with derating
- Storage temperature: -25 to +70 °C
- Humidity: 5 to 95%, no condensation, no dripping water
- Altitude: no derating to 1000 m, then 1% current derating per 100 m to 3000 m
- Environment tolerance: IEC 60721-3-3 class 3C3/3S2, IP66 enclosure
- Noise immunity: integrated C2 EMC filter, 10 m shielded motor cable at 4 kHz
- Power dissipation: 229 W at In and rated switching frequency
Inputs and Outputs
- Analog inputs:
- 1 bipolar differential ±10 V
- 1 voltage 0 to 10 V
- 1 current 0 to 20 mA, PTC probe support
- Digital inputs:
- 4 configurable 24 V DC sink/source
- 1 PTC probe input
- 1 pulse input up to 20 kHz
- Digital output:
- 1 configurable 24 V DC sink/source, 100 mA max
- Analog output:
- 1 output, 0 to 10 V or 0/4 to 20 mA, 10-bit resolution
- Relay outputs:
- 1 NO/NC contact plus 1 NO contact, 3 A at 250 VAC resistive load
- Pulse output:
- 1 output, 24 V, 32 kHz max, 0.1 A
- Safety inputs:
- 1 STO input plus 4 configurable safety inputs
- Functions: STO, SS1, SLS, SMS, GDL
Communication and Compatibility
- Built-in port: 1 RJ45 port for CANopen and Modbus Serial line
- Built-in protocols: CANopen, Modbus Serial line
- Expansion slot: 1 slot for optional modules
- Modbus TCP / EtherNet/IP
- PROFIBUS DP V1
- DeviceNet
- EtherCAT
- POWERLINK
- PROFINET
- Motor compatibility: asynchronous motors and synchronous PM motors
- Braking compatibility:
- External braking resistor connection
- Internal braking transistor for U22 and above
- Minimum external resistor 27 Ω
- Accessory compatibility:
- Graphic display terminal VW3A1111 / VW3A1101
- Remote display terminal
- UL Type 1 conformity kits
- DIN rail mounting plates
- GV2 circuit breaker mounting bracket
- 90-degree control module adapter
- External braking resistors
Installation Guide
- Mounting: vertical wall mount, ±10° tilt allowed
- Clearance: keep 100 mm free space around the drive
- Terminal torque: 1.2 to 1.5 N·m, Frame 4
- Wire size: 4 to 16 mm² recommended minimum cross-section
- Cable length: 10 m max shielded motor cable at 4 kHz for C2 and C3
- Derating: apply power derating above 4 kHz switching frequency
- Altitude: derate current 1% per 100 m above 1000 m
- Heat: plan airflow for 229 W dissipation at full load
Setup and Maintenance Convenience
- Fast commissioning: RJ45 port and Modbus Serial line work out of the box
- Clear diagnostics: relay outputs and configurable digital output report faults
- Flexible tuning: 2 to 16 kHz switching frequency adjusts noise and losses
- Simple service: front access to terminals and control module
- Display option: graphic terminal speeds up parameter copy and cloning
- Safety testing: STO input supports routine proof tests to SIL3/PLe
- Long life: IP66 housing resists dust and water jets in washdown areas
Certifications
- UL 508C, UL 61800-5-1
- CSA 22.2 N274
- EN/IEC 61800-3 category C2 and C3
- EN/IEC 61800-5-1
- IEC 61800-5-2 up to SIL3
- IEC 61508 SIL3
- IEC 13849-1 PLe
- IEC 60721-3-3 class 3C3/3S2
- RCM, EAC, KC
Note: the manufacturer does not publish a product-level cybersecurity certificate for this model. No Achilles statement appears in the April 2020 catalog or installation manual NVE41289.
Physical Data
- Dimensions (H×W×D): 521 x 320 x 335 mm
- Weight: 22.000 kg (48.501 lb)
- Enclosure: IP66 wall-mounting format
Package Contents
- 1 x ATV320U75N4W drive unit
- 1 x installation manual NVE41289
- 1 x safety information sheet
- Terminal hardware as shipped by Schneider Electric
- Optional items sold separately: display terminal, communication module, braking resistor, mounting kits
FAQ
- Can this drive run a permanent magnet motor?
- Yes. It supports sensorless vector control for synchronous PM motors, plus standard induction motor modes.
- Does the IP66 rating remove the need for a cabinet?
- Mostly yes. The sealed wall-mount housing allows direct mounting in washdown and dusty areas.
- What braking resistor should I order?
- Use an external resistor of at least 27 Ω. Size the wattage for your duty cycle.
- How do I connect to a plant network?
- Start with the built-in Modbus Serial line or CANopen port. Add an optional module for Ethernet, PROFINET, EtherCAT, or other fieldbuses.
- Can I mount it on a DIN rail?
- Yes, with the dedicated DIN rail mounting plates. The plates are separate accessories.
- What happens above 50 °C ambient?
- The drive still runs to 60 °C, but you must apply the catalog derating curve to output current.
- Field experience: the motor cable runs 30 m. Is that a problem?
- Likely yes at 4 kHz with the C2 filter. Keep shielded cable at 10 m or add an output filter and review EMC limits.
- Field experience: nuisance trips on a long motor lead. What first?
- Check shield grounding at both ends, then lower the switching frequency. Confirm the cable meets the 10 m C2 limit.
- Field experience: how do I clone settings across 20 machines?
- Use the graphic display terminal to copy parameters from one drive, then download to the rest.
- Field experience: the STO test takes time each shift. Any shortcut?
- Wire the STO input to your safety relay and log the proof test. The SIL3/PLe rating supports periodic testing without rewiring.
- Is a cybersecurity certificate available?
- No. Schneider Electric has not published a product-level cybersecurity statement for this model.
















There are no reviews yet.