Product details
ATV320U11N4WS | Schneider Electric Altivar Machine ATV320 1.1 kW IP65 Drive with Disconnect
This is the ATV320U11N4WS. It comes from the Altivar Machine ATV320 range by Schneider Electric. The drive runs 1.1 kW (1.5 HP) motors on 380 to 500 V three-phase power. One key detail sets it apart: a built-in Vario disconnect switch. That means no extra isolator on the panel. The IP65 case stays sealed. A category C2 EMC filter sits inside. Safety up to SIL3/PLe and a 599 Hz limit are also on board.
Name Plate
- Brand: Schneider Electric
- Model: ATV320U11N4WS
- Series: Altivar Machine ATV320
- Type: Three-phase variable speed drive, wall mount, IP65, with disconnect switch
Power Core
- Motor power: 1.1 kW (1.5 HP) at 380 to 500 V three-phase
- Nominal output current: 3.0 A at 4 kHz
- Transient current: 4.5 A for 60 s (150% of In)
- Output frequency: 0.1 to 599 Hz
- Switching frequency: 2 to 16 kHz, 4 kHz preset; derate above 4 kHz
- Overload torque: up to 200% Tn over-torque and 170% Tn braking torque
- Rating: one rating only; no Normal Duty or Heavy Duty split
Line Feed
- Voltage: 380 to 500 V three-phase, -15%/+10%, 50/60 Hz
- Input current: 5.0 A at 380 V; 3.8 A at 500 V
- Apparent power: 3.3 kVA at 500 V maximum
- SCCR: 5 kA maximum
- Losses: 40 W at In and rated switching frequency
Control Brain
- Async motor: U/F ratio (2-point, 5-point, energy-saving, quadratic) and sensorless flux vector control
- PM motor: sensorless vector control
- Analog path: 10-bit resolution on the analog output
I/O Branches
- Analog inputs
- 1 x bipolar differential ±10 V
- 1 x 0 to 10 V
- 1 x 0 to 20 mA
- PTC probe support
- Digital inputs
- 4 x 24 V DC, sink/source, configurable
- 1 x PTC probe
- 1 x pulse, up to 20 kHz
- Digital output: 1 x 24 V DC sink/source, 100 mA maximum
- Analog output: 1 x 0 to 10 V or 0/4 to 20 mA, 10 bits
- Relay outputs
- 1 x NO/NC contact
- 1 x NO contact
- 3 A at 250 VAC resistive load
- Pulse output: 1 x 24 V, 32 kHz maximum, 0.1 A
- Safety inputs
- 1 x STO
- 4 x configurable for SS1, SLS, SMS and GDL
- STO reaches SIL3 and PLe
Brake Path
- Method: external dynamic braking resistor
- Minimum value: 54 Ω
- Note: fit an outside resistor for fast stops
Network Branches
- Built-in port
- 1 x RJ45
- CANopen
- Modbus Serial Line
- Expansion slot
- Modbus TCP and EtherNet/IP
- PROFIBUS DP V1
- DeviceNet
- EtherCAT
- POWERLINK
- PROFINET
- Cyber certificate: none published by the maker
Weather and Noise
- Protection: IP65
- Running temperature: -10 to +50 °C with no derating; up to 60 °C with derating
- Storage temperature: -25 to +70 °C
- Humidity: 5 to 95%, no condensation, no dripping water
- Height: no derating to 1000 m; 1% current loss per 100 m up to 3000 m
- EMC: built-in C2 filter; 10 m shielded motor cable at 4 kHz (C2 and C3)
- Ambient class: IEC 60721-3-3 class 3C3/3S2
Body Size
- Dimensions (H×W×D): 340 x 250 x 200 mm
- Weight: 6.400 kg (14.109 lb)
- Terminal torque: 1.4 N·m power, 0.6 N·m control (Frame 2)
- Wire size: 2.5 to 6 mm² (Frame 2)
Where It Shines
- Standalone machines that need local lockout at the drive
- Conveyors and feeders on plant floors with dust
- Packaging cells with frequent cleaning and wet spray
- Pumps and small fans far from the main panel
- Retrofit jobs where adding a separate isolator is costly
- Remote skids that need one sealed unit for power and control
Mount and Wire
- Mount upright. A tilt of ±10° is fine.
- Leave 100 mm free space on all sides.
- Tighten power screws to 1.4 N·m and control screws to 0.6 N·m.
- Use wire from 2.5 to 6 mm².
- Keep shielded motor cable at or under 10 m for C2 EMC.
- Fit a resistor of at least 54 Ω for braking duty.
- Cut current 1% per 100 m above 1000 m altitude.
Commission and Care
- Use the disconnect switch to isolate the unit for service.
- Set up the drive over the RJ45 port with Modbus or CANopen.
- Add the VW3A1111 or VW3A1101 terminal for local control.
- Copy settings to a spare drive to cut downtime.
- Stay at 4 kHz unless you check the derating curve.
Match and Fit
- Runs standard async motors and PM motors.
- Works on 380 to 500 V grids at 50 or 60 Hz.
- Pairs with GV2 breakers using the mounting bracket.
- Takes DIN rail plates and UL Type 1 kits.
- Adds one fieldbus module through the free slot.
Approvals
- UL 508C and UL 61800-5-1
- CSA 22.2 N274
- EN/IEC 61800-3 category C2/C3
- EN/IEC 61800-5-1
- IEC 61800-5-2 up to SIL3 and IEC 61508 SIL3
- ISO 13849-1 PLe
- IEC 60721-3-3 class 3C3/3S2
- RCM, EAC and KC
In the Box
- 1 x ATV320U11N4WS drive with Vario disconnect switch
- 1 x printed installation manual
- 1 x safety sheet
- Terminal parts as packed by Schneider Electric
- Display terminal and brake resistor sold apart
FAQ
What does the S suffix add?
It means a Vario disconnect switch is built into the case. You can lock out the drive at the unit. No separate isolator is needed on the panel.
Why IP65 here and not IP66?
The switch door sets the rating. IP65 still blocks dust and low-pressure water jets. It suits most indoor washdown and dusty floors.
Can I still reach the terminals easily?
Yes. The switch sits on the case front. Wiring points stay clear. Leave the 100 mm air gap and you can service the unit fast.
Does the isolator affect safety ratings?
No. The STO input still reaches SIL3 and PLe. The switch is a lockout device; the safety chain stays on the dedicated inputs.
Is a separate panel door switch still required?
Check your local rules. Many sites accept the built-in switch as the local isolator. Others still want a door interlock for full lockout.
What is a common install slip?
Forgetting the motor cable limit. Stay at or under 10 m shielded to hold C2 EMC. Long runs may need extra filtering.