ATV320U11N4W | Schneider Electric Altivar Machine ATV320 1.1 kW IP66 Variable Speed Drive
The ATV320U11N4W is a ready-to-install three-phase drive from the Altivar Machine ATV320 series by Schneider Electric. It delivers 1.1 kW (1.5 HP) for 380 to 500 V three-phase supplies. A sealed IP66 wall-mount enclosure and a built-in category C2 EMC filter cut panel space and wiring work. The drive suits conveyors, packaging machines, pumps, fans and other compact machines. You get sensorless flux vector control, a 599 Hz maximum output frequency and full safety function support up to SIL3/PLe in one unit.
Technical Data
- Brand: Schneider Electric
- Model: ATV320U11N4W
- Series: Altivar Machine ATV320
- Module type: Three-phase variable speed drive, wall-mount, IP66
Core Ratings
- Motor power: 1.1 kW (1.5 HP) at 380 to 500 V three-phase
- Nominal output current In: 3.0 A at 4 kHz switching frequency
- Transient output current: 4.5 A for 60 s (150% of In)
- Output frequency: 0.1 to 599 Hz
- Switching frequency: 2 to 16 kHz, factory set 4 kHz; derate above 4 kHz
- Overload torque: up to 200% Tn over-torque and 170% Tn braking torque
Supply and Power
- Supply voltage: 380 to 500 V three-phase, -15%/+10%, 50/60 Hz
- Maximum input current: 5.0 A at 380 V; 3.8 A at 500 V
- Apparent power: 3.3 kVA at 500 V maximum
- SCCR: 5 kA maximum
- Power dissipation: 40 W at In and rated switching frequency
- Rating structure: single-rated output; no Normal Duty or Heavy Duty split
Control and Response
- Asynchronous motor: U/F ratio (2-point, 5-point, energy-saving, quadratic) and sensorless flux vector control
- Synchronous PM motor: sensorless vector control
- Speed reference resolution: analog reference resolved to 10 bits on the analog output path
Inputs and Outputs
- Analog inputs: 3 total, one bipolar differential ±10 V, one 0 to 10 V, one 0 to 20 mA, plus PTC probe support
- Digital inputs: 6 total, four configurable 24 V DC sink/source, one PTC probe, one pulse input up to 20 kHz
- Digital output: 1 configurable 24 V DC sink/source, 100 mA maximum
- Analog output: 1 output, 0 to 10 V or 0/4 to 20 mA, 10-bit resolution
- Relay outputs: 2 total, one NO/NC contact and one NO contact, 3 A at 250 VAC resistive load
- Pulse output: 1 output, 24 V, 32 kHz maximum, 0.1 A
- Safety inputs: 1 STO input plus 4 configurable safety inputs
Braking
- Dynamic braking: external braking resistor connection
- Braking transistor: external resistor required in this power range
- Minimum resistor: 54 Ω
Communication
- Built-in ports: 1 RJ45 port shared by CANopen and Modbus Serial Line
- Protocols: CANopen and Modbus Serial Line, built in
- Expansion: 1 slot for Modbus TCP/EtherNet/IP, PROFIBUS DP V1, DeviceNet, EtherCAT, POWERLINK or PROFINET modules
- Cybersecurity: no published product-level certification from the manufacturer
Environment and Immunity
- Protection rating: IP66
- Operating temperature: -10 to +50 °C without derating; up to 60 °C with derating
- Storage temperature: -25 to +70 °C
- Relative humidity: 5 to 95%, no condensation, no dripping water
- Altitude: no derating to 1000 m; derate 1% per 100 m from 1000 to 3000 m
- EMC immunity: integrated category C2 filter; 10 m shielded motor cable at 4 kHz (C2 and C3)
- Ambient class: IEC 60721-3-3 class 3C3/3S2
Physical
- Dimensions (H×W×D): 340 x 250 x 200 mm
- Weight: 6.000 kg (13.227 lb)
- Terminal torque: 1.4 N·m power, 0.6 N·m control (Frame 2)
- Wire cross-section: 2.5 to 6 mm² recommended (Frame 2)
Installation Guide
- Mount vertically, ±10° tilt allowed.
- Keep 100 mm clearance around the drive for airflow.
- Use the IP66 enclosure outdoors or in washdown areas without an extra cabinet.
- Tighten power terminals to 1.4 N·m and control terminals to 0.6 N·m.
- Size wires between 2.5 and 6 mm² for Frame 2.
- Keep shielded motor cables within 10 m to hold C2 EMC performance.
- Add an external braking resistor of at least 54 Ω when you need fast stops.
- Derate current 1% per 100 m above 1000 m altitude.
Setup and Maintenance
- Commission through the RJ45 port with Modbus or CANopen.
- Use the optional VW3A1111 or VW3A1101 graphic terminal for local setup.
- Clone settings between drives to cut downtime.
- The sealed IP66 housing needs no cabinet filter changes.
- Factory setting of 4 kHz keeps acoustic noise and losses low.
- Raise switching frequency only after checking derating.
Compatibility Notes
- Runs standard asynchronous motors and synchronous PM motors.
- Fits 380 to 500 V three-phase networks, 50 or 60 Hz.
- Works with GV2 circuit breakers using the mounting bracket.
- Accepts DIN rail mounting plates and UL Type 1 conformity kits.
- Adds fieldbus options through the single expansion slot.
Certifications
- UL 508C and UL 61800-5-1
- CSA 22.2 N274
- EN/IEC 61800-3 category C2/C3
- EN/IEC 61800-5-1
- IEC 61800-5-2 up to SIL3 and IEC 61508 SIL3
- ISO 13849-1 PLe
- IEC 60721-3-3 class 3C3/3S2
- RCM, EAC and KC
Package Contents
- 1 x ATV320U11N4W drive
- 1 x printed installation manual
- 1 x safety information sheet
- Terminal hardware as shipped by Schneider Electric
- Display terminal and braking resistor sold separately
FAQ
What motor size does this drive run?
It runs a 1.1 kW (1.5 HP) three-phase motor at 380 to 500 V. The 3.0 A nominal output covers standard four-pole motors in this class.
Can I mount it outdoors?
Yes. The IP66 enclosure resists dust and water jets. Keep the 100 mm clearance and stay within the -10 to +50 °C range without derating.
Do I need a braking resistor?
Only for fast stops or high inertia loads. Connect an external resistor of at least 54 Ω to the braking terminals.
Which networks can it join?
CANopen and Modbus Serial Line work out of the box on the RJ45 port. Add a module for EtherNet/IP, PROFINET, EtherCAT, POWERLINK, DeviceNet or PROFIBUS DP V1.
Does it meet machine safety standards?
Yes. The STO input reaches SIL3 and PLe. SS1, SLS, SMS and GDL functions are also available through the configurable safety inputs.
What do installers often get wrong?
Two things. First, long motor cables: stay at or below 10 m shielded to keep C2 EMC. Second, switching frequency: above 4 kHz the drive derates, so check the curve before you raise it.
How do I recover a replacement drive fast?
Save the configuration on a graphic terminal or over the bus. Load the same file into the new unit. This avoids manual re-entry and cuts restart time.
Is there a cybersecurity certificate?
Schneider Electric does not publish a product-level cybersecurity certificate for this model. Secure the network layer and limit remote access on your side.