Product details
ABB AI910B 3KDE175512L9100 Overview
- ABB 3KDE175512L9100 (AI910B) – S900 analog input module for hazardous areas
- Installs directly in Zone 2 hazardous locations – reduces marshalling costs
- Accepts 4…20 mA loop-powered 2-wire transmitters
- Hot-swap capable – replace during operation without power interruption
- ATEX certified for Zone 2, works with sensors in Zone 0/1/2
Key Features & Benefits
- Hazardous area ready
- ATEX Zone 2 certification – safe for explosive environments
- Intrinsic safety connections for field devices in Zone 0/1/2
- Operational flexibility
- Hot Configuration in Run – change settings online
- Hot Swap functionality – replace module without system shutdown
- Redundancy ready – power and communication redundancy supported
- Diagnostics & maintenance
- Advanced self-diagnostics – simplifies troubleshooting
- Short circuit and break detection per channel
- FDT/DTM support – detailed configuration and diagnostics
- Protection & durability
- G3 coating – withstands corrosive atmospheres (ISA-S71.04)
- Electrical isolation: input/bus and input/power isolated
- Common return for all 4 inputs
Technical Specifications
- General information
- Brand: ABB
- Model: 3KDE175512L9100 (AI910B)
- Series: S900 I/O System Type B
- Module type: Analog Input (AI4-B)
- Input characteristics
- Channels: 4 differential inputs
- Signal type: 4…20 mA (loop-powered 2-wire transmitters)
- HART: Not supported
- SOE: Not applicable
- Intrinsic safety: Yes – for Zone 0/1/2 sensors
- Isolation & protection
- Electrical isolation: input to bus, input to power
- Short circuit detection per channel
- Wire break detection per channel
- Common return for all inputs
- Redundancy support
- Power redundancy: yes (via S900 system)
- Communication redundancy: yes (PROFIBUS DP)
- Module redundancy: no (individual module non-redundant)
Environmental & Certification
- Hazardous location
- ATEX: Zone 2 certified
- Installation area: Zone 2 (module), sensors in Zone 0/1/2
- Climatic conditions
- Operating temperature: -20°C to +60°C
- Humidity: Max 93% ±3% at 40°C (non-condensing)
- Corrosion protection
- G3 coating: Meets ISA-S71.04 for corrosive environments
- Compliance
- CE mark: Yes
- RoHS: Directive 2011/65/EU (EN 50581:2012)
- WEEE: Directive 2012/19/EU, Small Equipment category
Mechanical Specifications
- Dimensions (W×H×D)
- Width: 20 mm (0.79 in)
- Height: 104 mm (4.09 in)
- Depth: 104 mm (4.09 in)
- Weight
- 0.13 kg (0.29 lbs) – lightweight design
- Mechanics
- S900 system format – fits standard S900 backplanes
- Type B mechanics for Zone 2 installation
Installation Guidelines
- Hazardous area installation
- Suitable for Zone 2 directly – follow ATEX installation rules
- Connect intrinsically safe sensors from Zone 0/1/2
- Mounting
- Snap onto S900 DIN rail base (sold separately)
- Requires S900 power and communication modules
- Wiring
- Use shielded twisted pair for 4-20mA signals
- Observe common return wiring for all channels
System Integration
- Communication
- PROFIBUS DP interface – connects to ABB or third-party controllers
- Redundant PROFIBUS supported
- Configuration
- FDT/DTM technology – use any FDT frame application
- Hot configuration – change parameters while running
- Compatibility
- Works with all S900 I/O system components
- Mixes with digital, temperature, and other analog modules
Package Contents & Warranty
- Box includes:
- 1× ABB AI910B (3KDE175512L9100) analog input module
- Product documentation leaflet
- ATEX certificate reference
- Mounting instructions
- Warranty: 12 months against manufacturing defects
- Certifications: ATEX, CE, RoHS, WEEE compliant
Shipping Information
- Express couriers: FedEx, UPS, DHL – insured worldwide
- Handling time: Ships within 24 hours on business days
- Tracking: Email notification with tracking number
Frequently Asked Questions
- Q: Can AI910B be used in Zone 1 directly?A: No – module is certified for Zone 2 only. For Zone 1, use S900 Type A modules (e.g., AI910A).
- Q: Does it support HART protocol?A: No – AI910B is for 4-20mA analog signals only. For HART, choose AI920B model.
- Q: How do I power 2-wire transmitters?A: Module provides loop power internally – no external power supply needed for sensors.
- Q: Can I hot-swap while PROFIBUS is active?A: Yes – Hot Swap supported. Remove and insert module without interrupting bus communication.
- Q: What is G3 coating and why important?A: G3 coating protects against corrosive gases (H2S, SO2). Essential for chemical plants and refineries.
- Q: How many AI910B modules per S900 station?A: Up to 20 modules per segment – depends on power budget and PROFIBUS addressing.
- Q: Does it work with Siemens PLC?A: Yes – PROFIBUS DP is open standard. Use GSD file for integration.
- Q: What’s the difference between AI910B and AI920B?A: AI920B adds HART communication. AI910B is basic 4-20mA with diagnostics.
Selection Guide
- Choose AI910B if you need:
- Basic 4-20mA analog input in Zone 2
- Loop power for 2-wire transmitters
- Hot-swap and online configuration
- G3 corrosion protection
- Consider alternatives if:
- Need HART – choose ABB AI920B
- Zone 1 installation – select AI910A (type A)
- RTD/TC inputs – use AI930B temperature module
Contact Information
- Email: sales@powergearx.com – 24/7 sales support
- WhatsApp: +86 18030005825 – instant technical help
- Response time: Within 4 hours on business days
Copyright © 2026 Powergear X Automation Limited. All rights reserved.
Original Source: https://www.powergearx.com/
















There are no reviews yet.