Product details
Product Overview
- Honeywell XNXXSS2SS – XNX Universal Transmitter
- Isolated RS485 Modbus RTU output module
- Factory or field installable (by qualified engineer)
- For Cl₂ (Lo) gas – Chlorine detection
Technical Specifications – Tree Structure
- Model: XNXXSS2SS
- Brand: Honeywell
- Series: XNXX Universal Transmitter
- Type: Modbus RTU output module
- Gas & Range: Chlorine (Cl₂ Lo)
- Default range: 5.00 ppm
- Lower Detectable Limit: 0.15 ppm
- Cal gas range: 30–70% of full scale
- Default cal point: 2.0 ppm
- Performance:
- Response T50: < 20 sec
- Response T90: < 60 sec
- Accuracy: < ±0.2 ppm
- Communication:
- Physical: Isolated RS485
- Baud rate: 1200 – 19.2K
- Max nodes: 254 (XNX compatible)
- Functions: same as Foundation Fieldbus option
- Environment:
- Operating temp: -10°C to 55°C (14°F to 131°F)
- Installation:
- Option: factory installed in display module
- Or field install by qualified service engineer
- Connections: RS485+, RS485-, Drain
Expert Review – Manager’s Insight
- “Reliable chlorine detection for critical safety.”
- Easy Modbus integration – saves wiring time
- Accurate low-level Cl₂ measurement (0.15 ppm LOD)
- Works in harsh environments (-10°C to 55°C)
- Ideal for water treatment and chemical plants
Typical Applications & Compatible Equipment
- Water treatment – chlorine dosing control
- Chemical processing – leak detection
- Pulp & paper bleaching areas
- Pharmaceutical manufacturing
- Works with PLC, DCS, and SCADA via Modbus
Comparison with Similar Models
- XNXAMRSS – ammonia version (NH₃)
- XNXH2SS – hydrogen sensor module
- XNXO2SS – oxygen transmitter
- All share the same XNX platform and Modbus option
FAQ – Professional Questions
- Can I install the Modbus module myself?
- Yes, but only a qualified service engineer should do field installation.
- Does this module work with Foundation Fieldbus?
- No, Modbus and Fieldbus are mutually exclusive options.
- How many transmitters can I connect?
- Up to 254 XNX-compatible units on one Modbus network.
- What is the default calibration gas value?
- Default cal point is 2.0 ppm Cl₂.
- Is the output isolated?
- Yes, RS485 output is fully isolated for noise immunity.
Experience-Based Q&A & Buying Guide
- “I need fast response for safety shutdown.”
- Choose this model – T90 < 60 sec, T50 < 20 sec.
- “What if my ambient temp exceeds 50°C?”
- Operating range is -10°C to 55°C – use sunshade or cooling if higher.
- “Can I use a longer RS485 cable?”
- Keep total length under 1200 m for reliable communication.
- Warranty & Shipping
- 12-month warranty against defects.
- 24-hour dispatch – ships via FedEx, UPS, or DHL.
Selection Guide
- Confirm gas type – this unit is for Chlorine (Cl₂ Lo)
- Check your network protocol – Modbus RTU required
- Verify temperature range in your plant
- Choose factory-installed option for faster startup
For inquiries, contact:
sales@powergearx.com
+86 18030005825 (WhatsApp)
Copyright © 2026 Powergear X Automation Limited. All rights reserved.
Original Source: https://www.powergearx.com/