Product details
Product Overview
- Honeywell XNXXSM1SS – Smart Sensor for Nitric Oxide (NO)
- Output module with isolated RS485 for Modbus networks
- Installed in display module or by a qualified engineer
- Supports multi-drop network with up to 254 nodes
Technical Data
- Gas detected: NO (Nitrogen Monoxide)
- Default range: 100 ppm
- Lower detectable limit: 3 ppm
- Cal gas range: 30‑70% of full scale
- Default cal point: 50 ppm
- Response time (T50): <15 sec
- Response time (T90): <30 sec
- Accuracy: ±2 ppm
- Operating temperature: -20°C to 55°C (-4°F to 131°F)
Communication & Physical Layer
- Protocol: Modbus RTU
- Baud rate: 1200 to 19.2K
- Connections: RS485+, RS485-, Drain
- Isolated RS485 – robust against noise
- Max nodes: 254 XNX transmitters only
Expert Review
- “Fast, accurate NO detection for safety and process control.”
- “Isolated Modbus output simplifies integration with PLCs.”
- “Reliable even in harsh industrial environments.”
- “Easy to install and calibrate with minimal downtime.”
Manager’s Insight
- “Great value for continuous NO monitoring in plants.”
- “Recommended for emission control and worker safety.”
- “Supports long‑distance communication via RS485.”
- “Reduces wiring cost compared to analog systems.”
Applications & Compatible Devices
- Industrial exhaust stacks – emission compliance
- Chemical plants – leak detection
- Power generation – NOx monitoring
- Pharmaceutical labs – fume hood safety
- Environmental monitoring stations
- Works with any Modbus RTU master (PLC, DCS, SCADA)
Frequently Asked Questions
- Is the sensor pre‑calibrated?
Yes, it is factory calibrated but field calibration is recommended. - What is the cable length limit?
Up to 1200 meters with shielded twisted‑pair cable. - Can I use this with other gas sensors?
No, this is specifically for Nitric Oxide (NO). - Does it have a display?
Only when installed in the display module (optional). - Is the module hot‑swappable?
No, power off before installation or removal.
Experience‑based Q&A
- Why is the reading unstable?
Check wiring and grounding. Avoid nearby high‑voltage cables. - How often to calibrate?
Every 3‑6 months depending on application and environment. - Can I change the range?
No, the range is fixed at 100 ppm for this model.
Selection Guide
- Confirm your gas is Nitric Oxide (NO).
- Ensure your network supports Modbus RTU.
- Check temperature stays within -20°C to 55°C.
- Order a display module if local readout is needed.
- Consider spare sensors for critical applications.
Warranty, Shipping & Contact
- Warranty: 12 months from purchase date
- Dispatch: within 12‑24 hours
- Shipping: FedEx, UPS, DHL (tracked)
- Inquiries: sales@powergearx.com
- WhatsApp: +86 18030005825
Comparison with Similar Models
- Honeywell XNXXSM2SS (higher range, different gas)
- Honeywell XNXXAM1SS (analog output version)
- Honeywell XNXXFM1SS (Foundation Fieldbus option)
Copyright © 2026 Powergear X Automation Limited. All rights reserved.