Product details
Product Overview
- TWDDMM24DRF is a discrete I/O module from the Twido series.
- It provides 16 DC inputs (24 V) and 8 relay outputs.
- Compact design with spring terminal blocks for easy wiring.
- Supports sink or source logic, flexible for most PLC systems.
- Ideal for small to medium automation control tasks.
Key Technical Data
- Brand: Schneider Electric
- Model: TWDDMM24DRF
- Inputs: 16 discrete, 24 V DC, 7 mA each
- Outputs: 8 relay outputs, 2 A per channel
- Input impedance: 3.4 kΩ
- Filter time: 8 ms (both state 0 and 1)
- Response time: ≤ 7 ms
- Isolation: 1500 Vrms (photocoupler)
- Common point: 1I / 2O configuration
Power & Environment
- Current consumption: 10 mA (5 V DC, all off) / 45 mA (24 V, all on) / 65 mA (5 V, all on)
- Operating temperature: 0…55 °C
- Storage temperature: -25…70 °C
- Protection: IP20 (front face)
- Certifications: CSA, UL, CE marked
Installation & Wiring
- Spring terminal blocks (TB_1, TB_2) for secure connections.
- Terminal labels clearly mark input numbers (IN_DIS#0~15) and commons (COM0_POS/NEG).
- Outputs use COM1#0-3 and COM2#4-7 commons.
- Supports both sink and source wiring without extra components.
Compatibility & Use Cases
- Works with Twido PLC base units and standalone.
- Suitable for conveyor control, packaging machines, and small assembly lines.
- Ideal for HVAC, lighting control, and simple sequencing tasks.
Expert Review
- “Reliable workhorse for discrete control. The relay outputs handle inductive loads well.”
- “Fast response and clear terminal labeling reduce installation errors.”
Manager’s Insight
- “Cost-effective choice for OEMs. Stock availability and 12-month warranty add value.”
- “Easy to integrate into existing Twido systems – no rewiring headaches.”
FAQ – Frequently Asked Questions
- Can I use this module with 12 V sensors?
No, the input voltage range is 20.4…28.8 V DC only. - What is the maximum current per common?
7 A per output common (COM1 or COM2). - Does it support PNP or NPN sensors?
Both sink and source logic, so it works with PNP (source) and NPN (sink). - How do I connect the common terminals?
Use COM0_POS for inputs and COM0_NEG if needed – see terminal diagram. - Is the module hot-swappable?
No, always power off the system before inserting or removing the module. - What is the typical lifespan of the relay outputs?
Over 100,000 cycles at rated load (resistive).
Selection Guide
- Choose this module if you need 16 inputs and 8 relay outputs in one compact unit.
- For all-transistor outputs, consider Twido‑DMM…DRF variants (not this model).
- Check your total output current: each channel 2 A, common max 7 A.
- Verify input impedance matches your sensor output (3.4 kΩ typical).
- If your ambient temperature exceeds 55°C, use a forced-air cooling cabinet.
Delivery & Support
- Shipping: Ships within 12‑24 hours after order confirmation.
- Carriers: FedEx, UPS, DHL – worldwide express.
- Warranty: 12 months against manufacturing defects.
- Package includes: Module, terminal blocks, and user manual (digital).
Contact Information
- Email: sales@powergearx.com
- WhatsApp: +86 18030005825
Copyright © 2026 Powergear X Automation Limited. All rights reserved.
Original Source: https://www.powergearx.com/













There are no reviews yet.