Over 50,000 hot-selling automation module components.

MTL4706 2-Channel Safety Barrier | ATEX/FM Certified

0 Reviews
12 in stock
  • 100% genuine products in stock with fast delivery.
  • 30-day return policy for quality assurance.
  • 12-month warranty for peace of mind.
SKU: MTL4706

Product details

MTL4706+ 2-Channel Safety Barrier: Ultra-Accurate Hazardous-Area Protection

Key Technical Data

  • Brand/Model: MTL4706+
  • Channels: 2 independent
  • Output: 4-20mA (negative-earth)
  • Accuracy: ±2μA
  • Voltage Output: ≥16V at 20mA
  • Load Resistance: 250Ω ±5%
  • Temperature Range: -20°C to +60°C
  • Safety Rating: 28V, 300Ω, 93mA

Installation & Compatibility

  • DIN-rail mounting (0.65W power dissipation)
  • Works with all 2-wire 4/20mA transmitters
  • Bussed-power compatible (20-35V range)
  • Max cable: 0.13μF capacitance, 4.2mH inductance

Certifications & Warranty

  • ATEX/IECEx, FM, CSA certified
  • 12-month warranty against defects
  • BASEEFA IIC and FM A/B safety approvals

FAQ

  • Q: Can it power 3-wire transmitters?
    A: Designed for 2-wire only
  • Q: Is external grounding required?
    A: Yes, earth terminal provided
  • Q: Maximum operating temperature?
    A: 60°C (140°F)

Additional information

Weight0.11 kg
Dimensions100 × 100 × 20 mm

Customers Reviews

There are no reviews yet.

Be the first to review “MTL4706 2-Channel Safety Barrier | ATEX/FM Certified”

Your email address will not be published. Required fields are marked *

Back to Top
Product has been added to your cart