Product details
Product Overview
MCC91A-0020-5E3-4-000 is a compact inverter from SEW-EURODRIVE. It belongs to the MOVITRAC classic series. This size 0S unit delivers 0.55 kW for asynchronous and synchronous motors. It works without an encoder. A 4Q brake chopper is built in. The drive suits cabinet mounting in industrial automation. It combines a universal 3 x AC 200-500 V supply with an integrated EMC filter. Commissioning stays simple thanks to cage-clamp terminals and a plug-in gateway slot.
Key Technical Data
- Brand: SEW-EURODRIVE
- Model: MCC91A-0020-5E3-4-000
- Series: MOVITRAC classic (MCC91A)
- Module type: Compact monolithic inverter, size 0S
- Rated motor power: 0.55 kW at 400 V (ASM)
- Supply voltage: 3 x AC 200-500 V, 50-60 Hz, +/-5%
- Nominal output current: 2.0 A at 4 kHz PWM
- Apparent output power: 1.4 kVA
- Nominal mains input current: 1.8 A at 400 V
- Overload capacity: 150% I_N for 30 s; 75% I_N continuous at 0 Hz
- DC link voltage: 560 V nominal, 980 V maximum
- PWM frequency: 4 / 8 / 16 kHz, adjustable
- Maximum output frequency: 599 Hz
- Minimum braking resistance: 90 Ω
- Brake chopper continuous power: 1.4 kW
- Power loss: 11 W (power section), 1 W (24 V supply)
- Control response: binary and analog setpoints onboard
- Resolution and linearity: set by the connected control signal and gateway option
Environment and Immunity
- Operating temperature: -10 to +40 °C, class 3K22, non-condensing
- Storage temperature: -25 to +70 °C, class 1K21, non-condensing
- Humidity: non-condensing per class 3K22
- Protection rating: IP20 per EN 60529, with line and motor connectors plugged in
- EMC filter: limit value category C2 per EN 61800-3
- Interference immunity: integrated EMC filter cuts conducted noise on the mains side
- Weight: 1.7 kg
Installation Guide
- Mount the unit vertically inside a cabinet.
- Keep the IP20 rating in mind. Plug in the line and motor connectors.
- Use the cage-clamp terminals X1 and X2 for wiring.
- Some terminals are spring-loaded for fast connection.
- Wire the braking resistor with at least 90 Ω.
- Keep the 24 V supply separate from power cables.
- Check the C2 EMC limit. Add external filtering if the site needs it.
Setup and Maintenance
- Set motor data with the CBG keypad or the CDM11A diagnostic module.
- Choose the PWM frequency: 4, 8 or 16 kHz.
- Use binary or analog setpoints for standalone control.
- The diagnostic module speeds up fault finding.
- Plug-in terminals cut downtime during replacement.
- No encoder wiring is needed. This saves setup time.
Compatibility Notes
- Runs asynchronous and synchronous motors without an encoder.
- Fits the CFX11A gateway slot for fieldbus control.
- Supported fieldbuses: PROFINET, EtherNet/IP, EtherCAT with SBus PLUS, Modbus TCP.
- The CFC11A module links up to 8 inverters to one gateway.
- The CSO safety option adds STO up to PL d.
- The CBG keypad and CDM11A module fit the same unit.
- No fieldbus is onboard. A gateway is required for network control.
Approvals and Standards
- EMC emission: category C2 per EN 61800-3.
- Protection: IP20 per EN 60529.
- Climate classes: 3K22 and 1K21 per IEC 60721.
- Safety option: STO up to PL d with the CSO module.
Packing List
- 1 x MCC91A-0020-5E3-4-000 inverter
- 1 x printed quick start guide
- Terminal covers as shipped
- Gateway, keypad, safety module and braking resistor sold separately
FAQ
Q: Can this drive run a motor without an encoder?
A: Yes. It controls asynchronous and synchronous motors in encoderless mode. Setup stays quick and wiring stays lean.
Q: How do I connect the drive to a PLC network?
A: Add the CFX11A gateway. It supports PROFINET, EtherNet/IP, EtherCAT with SBus PLUS and Modbus TCP. No fieldbus port sits onboard.
Q: What braking resistor should I choose?
A: Use a resistor of at least 90 Ω. The built-in chopper handles 1.4 kW continuous. Match the resistor to your duty cycle.
Q: Is the drive ready for safety functions?
A: Not by default. Fit the CSO module to get STO up to PL d. Plan this at order time.
Q: How many drives can share one gateway?
A: Up to 8 inverters can share one gateway with the CFC11A module. This cuts cabling and cost per axis.
Q: What is the usual cause of overtemperature trips?
A: Most trips come from a blocked cabinet fan or tight mounting gaps. Keep airflow clear and stay within -10 to +40 °C. Also check that PWM settings match the load.















There are no reviews yet.