Product details
Quick Overview
The DDI161 is a digital input module from Sigmatek. Its article number is 05-006-161. It belongs to the DIAS automation bus system. The module reads 16 digital signals at +24 V level. It also filters noise on signal lines. As a result, readings stay stable in busy plants.
Technical Data Tree
- Brand: Sigmatek
- Model: DDI161
- Article No.: 05-006-161
- Series: DIAS
- Type: Digital input module
- Inputs
- Channel count: 16 digital inputs
- Input voltage: +24 V typical, +30 V max
- Low level: below +8 V
- High level: above +14 V
- Switching threshold: +11 V typical
- Input current: about 5 mA at +24 V
- Input delay: 5 ms typical
- Status display: green LEDs
- Power
- Supply voltage: 18 to 30 V DC
- DIAS bus +5 V draw: 30 mA typical
- DIAS bus +5 V draw: 40 mA max
- Terminal module
- Mating part: DKL 011
- Order code: 05-024-011
- Type: 17-pin spring terminal strip
- Environment
- Operating temperature: 0°C to +60°C
- Storage temperature: -20°C to +85°C
- Humidity: 0 to 95%, no condensation
- EMC: EN 61000-6-2, industrial area
- Shock resistance: EN 60068-2-27, 150 m/s²
- Protection class: IP 20
- Approvals
- UL: E247993
Best Fit Devices and Use Cases
- First, it fits DIAS bus racks in machine control panels.
- Also, it suits PLC setups that read many on/off sensors.
- Then, it works well with limit switches and push buttons.
- Next, it handles proximity sensors and light barriers.
- After that, it serves valve feedback and relay contacts.
- Finally, it helps in packaging, handling and assembly cells.
FAQ
Q: Can I use this card without the DKL 011 terminal?
A: No. The card needs the DKL 011 to connect field wires. So, order 05-024-011 with the module.
Q: What happens if a signal sits near 11 V?
A: The card may read it as high or low. Therefore, keep signals well above 14 V or below 8 V.
Q: Why do my inputs react slowly?
A: The card adds a 5 ms filter. As a result, short noise spikes are ignored. This is normal, not a fault.
Q: How do I check a channel fast?
A: Watch the green LED for that input. Then, toggle the sensor. If the LED blinks, wiring is fine.
Q: Can I mount it in a cold room?
A: Only if the room stays at 0°C or above. For colder sites, use a heated cabinet. Otherwise, readings may drift.
Q: What is a common wiring mistake?
A: Mixing up the +24 V supply and the DIAS +5 V bus. Keep them apart. Also, check terminal labels twice.
Q: How much current does the bus draw?
A: Expect about 30 mA from the +5 V rail. Peak draw can reach 40 mA. Plan the bus budget with this in mind.