Product details
Product Overview
- CI862 TRIO Communication Interface (3BUA000037R1)
- Connects TRIO/Genius I/O to AC 800M controllers
- Makes TRIO appear as native AC 800M I/O
- Life cycle status: Classic (mature, reliable)
- Key function
- Interface between AC 800M and TRIO remote I/O blocks
- Manages channel data for the controller
- Handles I/O configuration and scanning
- Additional port
- Provides connection for Hand Held Monitor
System Architecture
- Single module capacity
- One CI862 connects up to 30 TRIO blocks
- Connects to one TRIO LAN
- Controller capacity
- AC 800M supports up to 4 CI862 modules
- Can have 4 single LANs or 4 redundant LANs
- Maximum I/O points: 1000 TRIO/Genius points
- Redundancy
- Module redundancy: Yes
- Line redundancy: No
- CI862 can be set redundant for higher availability
Technical Specifications
- Communication details
- Protocol: ABB TRIO/Genius I/O
- Role: Master device
- Transmission speed: Not specified
- Bus capacity
- Max units on CEX bus: 4
- Connector types
- Phoenix (4-pin) – power and signals
- DB9 male – Hand Held Monitor
- DB9 female – TRIO LAN connection
- Power consumption
- 24V consumption: 190 mA typical
Hot Swap & Compatibility
- Hot Swap support
- Yes – replace without powering down
- HI Controller compatibility
- No – not for High Integrity safety systems
- Use other modules for SIL-rated applications
Environmental & Certifications
- Operating conditions
- Temperature: +5 to +55°C operating
- Storage: -40 to +70°C
- Humidity: 5 to 95% non-condensing
- Protection
- IP20 rating (EN60529, IEC 529)
- Certifications
- CE marked
- WEEE compliant (2012/19/EU)
- RoHS compliance: Not specified
Dimensions & Weight
- Width: 59 mm (2.3 in)
- Height: 185 mm (7.3 in)
- Depth: 127.5 mm (5.0 in)
- Weight: 700 g (1.5 lbs)
Professional FAQ
- Q: How many TRIO I/O points can I connect total?A: Maximum is 1000 I/O points across all CI862 modules in one AC 800M controller.
- Q: Can I mix TRIO and other I/O types on same CEX bus?A: Yes. CI862 shares CEX bus with other communication modules. Total CEX units max is 12.
- Q: What does “Classic” life cycle status mean?A: Product is mature and stable. Still fully supported but not for new large projects. Good for expansions.
- Q: Does it support Genius I/O protocol or only TRIO?A: It supports both TRIO and Genius I/O protocols. Compatible with legacy Genius blocks.
- Q: What cable do I need for Hand Held Monitor?A: Use standard DB9 male-to-female serial cable. Pinout in product manual.
Selection & Purchase Guide
- I/O count: Calculate your TRIO points. Max 1000 per system, 30 blocks per CI862.
- Redundancy needed? Order two CI862 modules for redundant pairs.
- Existing system: Perfect for expanding classic AC 800M with TRIO I/O.
- Not for safety: Not compatible with HI controllers. Use safe I/O for SIL apps.
- Warranty: 12 months from invoice. Fast shipping via FedEx, UPS, DHL.
Shipping & Warranty
- Express shipping: FedEx, UPS, DHL – fully tracked and insured
- 12 months warranty: Covers defects in materials and workmanship