Product details
Product Overview
ATV930U22N4Z is a Schneider Electric variable speed drive from the Altivar Process ATV930 series. It suits three-phase supplies from 380 to 480 V. This cabinet integration version comes with IP20 protection. It also includes a built-in braking unit.
The drive offers dual ND/HD rating. Normal Duty gives 2.2 kW (3 HP) with 120% overload for 60 s. Heavy Duty gives 1.5 kW (2 HP) with 150% overload for 60 s. You get flexible motor control for asynchronous, synchronous PM, and synchronous reluctance motors.
Key Benefits
- Dual rating flexibility: One drive covers normal and heavy duty tasks.
- Built-in safety: STO function meets SIL3 and Cat. PL e.
- Open communication: Dual-port EtherNet/IP and Modbus TCP come standard.
- Expansion ready: One slot supports PROFINET, EtherCAT, CANopen, and more.
- Strong cybersecurity: Achilles Level 2 certified.
Technical Specifications
- Brand: Schneider Electric
- Model: ATV930U22N4Z
- Series: Altivar Process ATV930
- Module type: Three-phase variable speed drive, cabinet integration, IP20
- Motor power (ND): 2.2 kW (3 HP), 120% overload for 60 s
- Motor power (HD): 1.5 kW (2 HP), 150% overload for 60 s
- Supply voltage: 380 to 480 V three-phase, -15%/+10%, 50/60 Hz
- Output frequency: 0.1 to 599 Hz
- Switching frequency: 4 kHz nominal, with automatic derating above nominal
- ND input current: 4.3 A at 380 V; 3.8 A at 480 V
- ND output current: 5.6 A continuous; 6.7 A transient for 60 s
- HD input current: 3.1 A at 380 V; 2.9 A at 480 V
- HD output current: 4.0 A continuous; 6.0 A transient for 60 s
- Motor control: Open-loop and closed-loop vector control for async, PM, and reluctance motors
- Braking: Built-in chopper; external resistor required, 56 Ohm minimum
- SCCR: 50 kA maximum
- EMC filter: Category C2 integrated
I/O and Communication
- Analog inputs: 3 total; 2 configurable 0 to 10 V or 0/4 to 20 mA with probe input; 1 configurable 0 to +/-10 V
- Digital inputs: 8, 24 V DC, positive or negative logic
- Digital output: 1 assignable, configurable as PTO
- Analog outputs: 2, configurable 0 to 10 V or 0/4 to 20 mA
- Relay outputs: 3 total; 1 NO/NC plus 2 NO
- Safety inputs: 2 for STO
- Built-in ports: 1 Ethernet dual-port switch; 1 Modbus serial port
- Protocols: EtherNet/IP, Modbus TCP, Modbus RTU
- Expansion: Up to 3 I/O modules; 1 fieldbus option slot
Environmental and Physical Data
- Operating temperature: 0 to +40 C standard; derating up to +50 C
- Storage temperature: -40 to +70 C
- Humidity: 5 to 95%, non-condensing
- Altitude: Up to 1000 m no derating; derate 1% per 100 m above 1000 m
- Protection rating: IP20; bottom power terminals IP00
- Environmental class: IEC 60721-3-3 class 3C3 / 3S3 / 3M3
- Power dissipation: 98 W (ND) / 67 W (HD) at nominal load
- Minimum air flow: 38 m3/h
- Dimensions (H x W x D): 285 x 130 x 196 mm
- Terminal torque: 2.5 N.m
- Clearance: 100 mm above and below; 10 mm front
Installation Guide
- Mount the drive vertically inside a cabinet.
- Keep 100 mm clearance above and below the unit.
- Leave 10 mm free space at the front.
- Provide 38 m3/h minimum air flow.
- Tighten power terminals to 2.5 N.m.
- Use an external braking resistor of at least 56 Ohm.
- Follow EMC rules for Category C2 wiring.
Setup and Maintenance
- Start with the built-in Modbus or Ethernet port for quick commissioning.
- Use clear text menus for fast parameter access.
- Check fan flow and filter condition at regular intervals.
- Review overload history during scheduled service.
- Replace the braking resistor only with a rated part.
Compatibility Notes
- Works with asynchronous motors in open or closed loop.
- Supports synchronous PM and reluctance motors.
- Fits fieldbus modules such as PROFINET, PROFIBUS DP V1, CANopen, DeviceNet, EtherCAT, and POWERLINK.
- Accepts up to 3 extra I/O modules.
- Integrates with plant networks through EtherNet/IP and Modbus TCP.
Certifications
- UL 508C
- UL 61800-5-1
- EN/IEC 61800-3 category C2/C3
- EN/IEC 61800-5-1
- IEC 61508 SIL3
- ISO 13849-1 Cat. PL e
- Achilles Level 2
- REACH
- SEMI F47-0706
Packing List
- ATV930U22N4Z drive unit
- Installation manual reference NHA80932
- Safety and compliance documents
- Terminal labels and quick start guide
FAQ
Q: Can this drive run both normal and heavy duty loads?
A: Yes. It carries a dual rating. Normal Duty gives 2.2 kW. Heavy Duty gives 1.5 kW with higher overload.
Q: Does the drive include a braking resistor?
A: No. It has a built-in chopper. You must add an external resistor of at least 56 Ohm.
Q: Which motors does it support?
A: It supports asynchronous, synchronous PM, and synchronous reluctance motors.
Q: What is the default communication port?
A: The unit ships with a dual-port Ethernet switch and a Modbus serial port.
Q: Can I add more I/O later?
A: Yes. You can fit up to three extra I/O modules and one fieldbus module.
Q: From experience, what should I check first at startup?
A: Check motor nameplate data, wiring polarity, and STO input status before the first run.
Q: What causes frequent overload trips in panel builds?
A: Poor air flow and tight clearance are common causes. Keep 100 mm above and below the drive.
Q: How do I handle high altitude sites?
A: Derate the nominal current by 1% for every 100 m above 1000 m.
Q: Is the drive suitable for networked plants?
A: Yes. It supports EtherNet/IP and Modbus TCP natively, with Achilles Level 2 security.

















There are no reviews yet.