Product details
Product Brief – AAI543-H00/K4A00
- Type: Analog Output Module
- Brand: Yokogawa
- Model: AAI543-H00/K4A00
- Series: AAI543
- Outputs: 16 isolated channels, 4-20 mA
- HART: Built-in digital communication (HART protocol)
- Redundancy: Standard switch-over for redundant configurations
- Terminal: Includes KS Cable Interface Adapter (ATK4A-00)
Key Technical Data – Tree Structure
- Output
- Signal: 4 to 20 mA
- Channels: 16, isolated
- Load resistance: 0 to 750 Ω
- Accuracy: ±48 µA
- Update period: 10 ms
- Protection & Detection
- Withstanding voltage: 1500 V AC (1 min, output to system)
- Circuit-open detection: < 0.65 mA
- Drift: ±16 µA per 10 °C ambient change
- Power
- 5 V DC: 230 mA max
- 24 V DC: 540 mA max
- Communication & Connection
- HART: Yes (digital communication)
- External: Pressure clamp terminal, MIL connector, KS1 cable
- Physical
- Weight: 0.4 kg
- Adapter: KS Cable Interface (ATK4A-00) included
Expert Review
AAI543-H00/K4A00 delivers precise 4-20 mA control with ±48 µA accuracy. The 10 ms update rate supports fast loops. HART adds digital diagnostics and configuration. Redundant-ready design improves system reliability. A solid choice for critical process applications.
Manager’s Insight
This module reduces wiring complexity with the KS1 cable system. The 1500 V isolation protects the controller. Use it for valve positioning, pump speed, or actuator control. Its drift spec ensures stable output across temperature changes.
Compatible Devices & Applications
- Systems: Yokogawa CENTUM VP, ProSafe-RS, or any DCS accepting 4-20 mA
- Actuators: Control valves, dampers, variable speed drives
- Applications: Flow control, pressure regulation, temperature loops
- Industries: Oil & gas, chemical, power generation, water treatment
Comparison – Similar Models
- AAI543-H00/K4A00 – no HART, basic type
- AAI543-S50/K4A00 – with HART and special redundancy
- AAI143-H50 – 8-channel version, same family
FAQ – Professional Questions
- Q: What is the output accuracy of AAI543-H50/K4A00?
- A: ±48 µA over full range.
- Q: Does this module support HART communication?
- A: Yes, HART is built-in for digital configuration.
- Q: What is the maximum load resistance?
- A: 750 Ω at 24 V supply.
- Q: Can I use it in a redundant system?
- A: Yes, it has standard switch-over for redundancy.
- Q: What cable do I need for connection?
- A: Use KS1 dedicated cable or MIL connector.
Experience-based FAQ & Selection Guide
- Q: How to avoid ground loop issues?
- A: Use isolated outputs – this module provides channel isolation.
- Q: What happens if the load is shorted?
- A: The module limits current; it detects open circuit below 0.65 mA.
- Q: Can I calibrate the output without a HART communicator?
- A: Yes, use the DCS or software tools via HART.
- Q: Is the adapter included?
- A: Yes, K4A00 suffix includes the KS Cable Interface Adapter.
- Q: How to mount this module?
- A: It fits standard Yokogawa I/O racks (no extra bracket).
- Q: Does it support 0-20 mA output?
- A: No, it outputs 4-20 mA only.
Selection Guide – What to Consider
- Check your DCS compatibility – works with CENTUM VP and ProSafe-RS.
- Count your output points – 16 channels per module saves space.
- Need HART? – This model includes it; choose -H00 for non-HART.
- Load resistance – ensure your device stays within 0-750 Ω.
- Redundancy – select this for critical loops that cannot fail.
Warranty, Shipping & Support
- Warranty: 12 months against manufacturing defects.
- Dispatch: 12–24 hours after order confirmation.
- Couriers: FedEx, UPS, DHL (express delivery).
Contact Information
For inquiries: sales@powergearx.com
WhatsApp: +86 18030005825
Copyright © 2026 Powergear X Automation Limited. All rights reserved.
Original Source: https://www.powergearx.com/
















There are no reviews yet.