Over 50,000 hot-selling automation module components.

6ES7422-1BH11-0AA0 Siemens 16-Channel Digital Output | S7-400 SM 422

0 Reviews
In stock
  • 100% genuine products in stock with fast delivery.
  • 30-day return policy for quality assurance.
  • 12-month warranty for peace of mind.
SKU: 6ES7422-1BH11-0AA0
Brands:

Product details

Product Overview

  • Siemens 6ES7422-1BH11-0AA0 – digital output module for S7-400 systems
    • Part of the SIMATIC S7-400 SM 422 series
    • Provides 16 isolated digital outputs
    • Rated at 24 V DC with 2 A per channel
    • Clocked electronic short-circuit protection

Technical Specifications – Hierarchical View

  • Supply voltage
    • Rated value: 24 V DC
    • Lower limit: 20.4 V DC
    • Upper limit: 28.8 V DC
  • Current consumption
    • From load voltage L+ (no load): max. 30 mA
    • From backplane bus 5 V DC: max. 160 mA
  • Power loss
    • Typical: 5 W
  • Digital outputs
    • Number of outputs: 16 channels
    • Short-circuit protection: Yes (clocked electronic)
    • Response threshold: 2.8 to 6 A typical
    • Inductive shutdown voltage limit: -30 V
    • Can control digital inputs: Yes
  • Output ratings
    • Lamp load capacity: max. 10 W
    • Load resistance range: 24 Ω to 4 kΩ
    • Signal “1” voltage: min. L+ (-0.5 V)
    • Signal “1” rated current: 2 A
    • Signal “1” current range: 5 mA to 2.4 A
    • Signal “0” residual current: max. 0.5 mA
  • Switching performance
    • Output delay (resistive load): max. 1 ms (both transitions)
    • Resistive load switching frequency: max. 100 Hz
    • Inductive load (DC13) at 1 A: 0.2 Hz
    • Inductive load (DC13) at 2 A: 0.1 Hz
    • Lamp load frequency: max. 10 Hz
  • Group current limits
    • Up to 40°C: max. 3 A per group
    • Up to 60°C: max. 2 A (2 adjacent outputs each)
  • Cable length
    • Shielded: max. 1000 m
    • Unshielded: max. 600 m
  • Isolation & testing
    • Channel-to-channel isolation: Yes
    • Group isolation: 8 channels per group
    • Channel-to-backplane bus isolation: Yes
    • Test voltage: 500 V DC

Expert Review – Field Engineer’s Insight

  • This module handles heavy loads better than most competitors
  • Each output drives 2 A continuously – ideal for solenoid valves and contactors
  • Clocked short-circuit protection prevents damage from wiring mistakes
  • Inductive load switching is slow (0.1 Hz) – plan for this limitation
  • Group current derating at 60°C requires careful load distribution

Compatible Systems & Applications

  • Compatible PLC systems
    • Siemens SIMATIC S7-400 series
    • Works with all S7-400 CPUs (UR1, UR2, UR2-H racks)
    • Requires S7-400 backplane bus connection
  • Typical applications
    • Driving DC contactors and relays in motor control centers
    • Actuating solenoid valves in process automation
    • Controlling indicator lamps and small actuators
    • Interfacing with 24 V DC digital field devices

Installation & Wiring Guide

  • Mount the module in any S7-400 rack slot
  • Connect 24 V DC load supply to terminals L+ and M
  • Wire outputs to field devices using 0.5-2.5 mm² cable
  • Use shielded cable for runs over 600 m (max 1000 m)
  • Group outputs in pairs to share common return paths

Maintenance & Troubleshooting

  • No diagnostics function – check module status via PLC program
  • Monitor output current per group to avoid exceeding limits
  • If an output trips, the module auto-resets after fault removal
  • Replace the module without removing wiring (spring terminals)

Package Contents

  • 1x Siemens 6ES7422-1BH11-0AA0 output module
  • 1x front connector (screw-type, included)
  • 1x label strip for channel identification
  • Quick-start guide (multilingual)

Shipping & Warranty

  • 12-month warranty against manufacturing defects
  • Same-day dispatch (orders placed before 2 PM GMT+8)
  • Express shipping via FedEx, UPS, or DHL
  • Tracking number provided within 24 hours

Frequently Asked Questions

  • Can I parallel two outputs for higher current?
    • A: No, the module does not support output parallel connection for uprating.
  • Can I use two outputs to control one redundant load?
    • A: Yes, but only outputs from the same group can provide redundancy.
  • What is the maximum switching frequency for inductive loads?
    • A: At 1 A load, max 0.2 Hz. At 2 A load, reduce to 0.1 Hz.
  • Does this module detect open circuits or short circuits?
    • A: No diagnostics feature. The module only has short-circuit protection without reporting.
  • How do I derate the output current at high temperatures?
    • A: Above 40°C, limit group current to 2 A with only 2 adjacent outputs active.

Selection Guide – Which Module Do You Need?

  • Need 16 outputs at 2 A? Choose 6ES7422-1BH11-0AA0 (this module)
  • Need 32 outputs at 0.5 A? Choose 6ES7422-1BL00-0AA0
  • Need relay outputs? Choose 6ES7422-1HH00-0AA0
  • Need diagnostic capabilities? Choose 6ES7422-5BH00-0AB0

Contact & Support

Copyright © 2026 Powergear X Automation Limited. All rights reserved.
Original Source: https://www.powergearx.com/

Specifications

  • BrandSiemens
  • Part Number6ES7422-1BH11-0AA0
  • ConditionOriginal Brand New