Product details
SCP111-S Safety CPU Module by Sigmatek
The SCP111-S (20-890-111-S-E) is a safety CPU module from Sigmatek. It handles functional safety control and logic monitoring in industrial automation. This module meets SIL3 (EN IEC 62061) and PL e / Cat. 4 (EN ISO 13849). It uses an ARM Cortex-M microcontroller with 24 KB SRAM and 224 KB Flash. You can connect up to 16 safety I/O modules and handheld devices with emergency stop, confirmation, or key switches.
Technical Data
- Brand: Sigmatek
- Model / Part No.: SCP 111-S (20-890-111-S-E)
- Safety Level: SIL3 (EN IEC 62061), PL e / Cat. 4 (EN ISO 13849)
- Processing Unit: ARM Cortex-M microcontroller
- Memory: 24 KB SRAM, 224 KB Flash
- Expansion: Up to 16 safety I/O modules plus handheld devices with emergency stop, confirmation, or key switches
- Supply Voltage: +18 to +30 V DC (typical +24 V DC)
- Dimensions: 25 x 104 x 72 mm
- Protection Class: IP20
- Reliability: PFH = 2.00E-9/h, SFF = 99%, MTTFD = 1099 years, DC = 99%
- Temperature Range: Storage -20 to +85 °C; Environmental 0 to +60 °C
- Humidity: 0 to 95%, non-condensing
- Installation Altitude: 0 to 2000 m without derating; above 2000 m up to 5000 m with derating of maximum environmental temperature by 0.5 °C per 100 m
- Operating Conditions: Pollution degree 2
- Noise Emission: ≤ 70 dB
- EMC Resistance: EN 61000-6-2 (industrial area), EN 61000-6-7 (noise immunity industry functional safety, increased requirements per EN IEC 62061)
- EMC Noise Generation: EN 61000-6-4 (industrial area)
Installation Guide
- The +24 V supply connections (X3: pin 1 and pin 2) and GND supply connections (X3: pin 3 and pin 4) are internally bridged.
- To supply the module, connect only one +24 V pin (pin 1 or pin 2) and one GND pin (pin 3 or pin 4).
- You can use the bridged connections to loop the +24 V supply and GND supply further.
- Important: Do not exceed a total current of 6 A per connection when looping forward.
Commissioning and Maintenance Convenience
- The bridged supply terminals simplify wiring and reduce installation time.
- Compact 25 x 104 x 72 mm housing fits tight control cabinets.
- IP20 protection supports standard cabinet mounting.
- Wide temperature range from 0 to +60 °C suits most industrial environments.
- High diagnostic coverage (DC = 99%) and high SFF (99%) reduce maintenance effort.
Compatibility Notes
- Works with up to 16 safety I/O modules from the Sigmatek system.
- Supports handheld devices with emergency stop, confirmation, or key switches.
- Designed for functional safety applications per EN IEC 62061 and EN ISO 13849.
- EMC compliance covers industrial areas and functional safety noise immunity.
Certifications
- SIL3 according to EN IEC 62061
- PL e / Cat. 4 according to EN ISO 13849
- EMC: EN 61000-6-2, EN 61000-6-7, EN 61000-6-4
Package Contents
- 1 x SCP 111-S Safety CPU Module (20-890-111-S-E)
- 1 x Quick start guide (standard Sigmatek delivery)
FAQ
- Q: Can I use only one +24 V pin and one GND pin to power the module?
- A: Yes. The +24 V pins (X3: pin 1 and pin 2) and GND pins (X3: pin 3 and pin 4) are bridged internally. You need only one +24 V connection and one GND connection.
- Q: What is the maximum current when I loop the supply to other modules?
- A: The total current per connection must not exceed 6 A. Plan your loop wiring carefully.
- Q: How many safety I/O modules can I connect?
- A: You can connect up to 16 safety I/O modules. You can also add handheld devices with emergency stop, confirmation, or key switches.
- Q: Does this module work at high altitudes?
- A: Yes, up to 2000 m without derating. Above 2000 m and up to 5000 m, derate the maximum environmental temperature by 0.5 °C per 100 m.
- Q: What safety level does the SCP 111-S achieve?
- A: It achieves SIL3 (EN IEC 62061) and PL e / Cat. 4 (EN ISO 13849).
- Q: Can I use this module in a polluted environment?
- A: The module is rated for pollution degree 2. Use it in suitable enclosures or cabinets.
- Q: How do I know the module is reliable for long-term use?
- A: Key reliability values are PFH = 2.00E-9/h, SFF = 99%, MTTFD = 1099 years, and DC = 99%. These values support long-term safety operation.













There are no reviews yet.