Product details
🔌 Product highlights
The ABB DI890 Digital Input Module (article 3BSC690073R1) provides 8 intrinsically safe channels for hazardous areas. It directly connects NAMUR proximity sensors or volt‑free contacts without external barriers. Each channel is galvanically isolated. Perfect for Ex Zone 0/2 applications with S800 I/O.
Need expert help? sales@powergearx.com or WhatsApp +86 18030005825.
🧩 Model identity – DI890
- ABB DI890 – Digital Input Module · article 3BSC690073R1
- ⤷ 8 channels · Intrinsic Safety on each channel
- ⤷ Accepts NAMUR proximity sensors or volt‑free contacts
- ⤷ Galvanic isolation: channel‑to‑channel, to ground, to bus
- ⤷ Line fault detection for NAMUR (no external parts)
- ⤷ For volt‑free contacts: external resistors needed for fault detection
- ⤷ LEDs: Run (green), Fault (red), Warning (yellow) + per‑channel status
⚙️ Core technical data
- Electrical & isolation
➜ Rated insulation 50 V · dielectric test 500 V a.c.
➜ Current limiting built‑in for sensor power - Filter & response
➜ Digital filter selectable: 2, 4, 8, 16 ms
➜ Analog filter 1 ms fixed - Power consumption
➜ +5 V ModuleBus: typ 120 mA · max <150 mA
➜ +24 V external: typ 50 mA · max <70 mA · total dissipation 1.4 W - Temperature range
➜ Operating 0°C to +55°C · storage -40°C to +70°C
➜ Vertical mount in compact MTU: max 40°C - Dimensions & weight
➜ Width 45 mm · Depth 102 mm (111 mm with connector)
➜ Height 119 mm · Weight 0.2 kg (0.44 lb)
🔧 Compatible MTUs
- For Ex applications
TU890 Compact MTU · 2‑wire connection without extra terminals - For non‑Ex applications
TU891 Compact MTU · simple 2‑wire field wiring - Keying code AA
✅ Certifications at a glance
- Hazardous area
ATEX/IECEx Zone 2 (interface to Zone 0) · cFMus Class I Div 1/Zone 0 - Marine
ABS, BV, DNV, LR — full approval - Environment
IP20 · G3 corrosion · CE · RoHS · WEEE · EN 61000-6-2/4
📦 Delivery & warranty
- Warranty
12 months against defects · full parts & labor - Shipping
FedEx, UPS, DHL · fast global delivery · tracking included - In the box
1x DI890 module · quick start guide
🏭 Typical applications
- Industries
Oil & gas · chemical · pharmaceutical · mining · hazardous processing - Best use
Intrinsically safe NAMUR sensors in Zone 0/1/2 · volt‑free contact monitoring with line fault detection
❓ Professional FAQ (real‑world advice)
- Q: What is the advantage of DI890 over standard DI modules?
A: DI890 has built‑in Intrinsic Safety components on every channel. You can connect sensors directly in hazardous areas (Zone 0/1/2) without external zener barriers or isolators. Saves space and cost. - Q: Can I use volt‑free contacts with line fault detection?
A: Yes, but you must add external resistors. Connect a 1 kΩ resistor in parallel with the contact and a 4.7 kΩ resistor in series. This lets the module detect open/short circuits in the field wiring. - Q: Which MTU should I order with DI890?
A: For Ex applications, use TU890. For non‑Ex, use TU891. Both are compact MTUs that allow direct 2‑wire connection without extra terminals. TU890 maintains intrinsic safety. - Q: What does the yellow Warning LED indicate?
A: The Warning LED lights for internal process supply supervision or loop faults. Check channel status LEDs to identify which channel has a line fault (e.g., broken wire or short). - Q: Is DI890 approved for SIL or high‑integrity systems?
A: No, DI890 is not High Integrity or SIL rated. It’s a standard S800 I/O module with intrinsic safety. For SIL applications, use AC 800M High Integrity with separate safety barriers.
Copyright © 2026 Powergear X Automation Limited. All rights reserved.
Original Source: https://www.powergearx.com/