Product details
EPP1321-0060 – 1-Channel EtherCAT to EtherCAT P Supply Module
The BECKHOFF EPP1321-0060 converts EtherCAT to EtherCAT P in IP67 enclosures. It supplies up to 3 A per US and UP for sensors and actuators. The module supports flexible topology branches. It features status LEDs for EtherCAT, US, and UP. The M8 connectors enable quick plug‑in wiring.
Key Features
- 1‑channel converter – EtherCAT input to EtherCAT P output
- 3 A per US and UP – powers many sensors and actuators
- IP 67 protection – suitable for harsh industrial environments
- Status LEDs – indicate EtherCAT, US, and UP states
- M8 connectors – 4‑pin, shielded, EtherCAT‑P‑coded
- Flexible voltage feed – optional US/UP forwarding
- CE and UL (in preparation) – global compliance
Technical Data
- Brand: BECKHOFF
- Model: EPP1321‑0060
- Series: EtherCAT Box
- Module type: EtherCAT to EtherCAT P Supply
- Task: Converter from EtherCAT to EtherCAT P
- Number of channels: IN: 1 x EtherCAT, OUT: 1 x EtherCAT P
- Nominal voltage: 24 V DC (-15 % / +20 %)
- Total current feed‑in: max. 3 A per US and UP
- Current consumption (US): typ. 100 mA
- Current rating per port: max. 3 A per US and UP
- Power connection (feed): 1 x M8 male socket, 4‑pin
- Power connection (downstream): 1 x M8 female socket, 4‑pin
- Bus interface: M8 socket, shielded, screw type, EtherCAT‑P‑coded
- Protocol: EtherCAT / EtherCAT P
- Data transfer rate: 100 Mbit/s
- Distributed clocks: not supported
- Weight: approx. 90 g
- Operating temperature: -25…+60 °C
- Storage temperature: -40…+85 °C
- Vibration/shock: EN 60068‑2‑6 / EN 60068‑2‑27
- EMC immunity/emission: EN 61000‑6‑2 / EN 61000‑6‑4
- Protection class: IP 65/66/67 (EN 60529)
- Installation position: variable
- Accessories: ZK700x (EtherCAT P cables), ZK1090, ZK2020 (M8 power cables)
Expert Review
The EPP1321‑0060 simplifies the transition from standard EtherCAT to the power‑over‑EtherCAT P technology. Its 3‑A output per line supports a wide range of field devices. The IP67 rating ensures reliable operation in wet or dusty areas. The M8 connectors are robust and easy to mate. For branched systems, combine with EPP1332‑0001 (voltage refresh) or EPP1342‑0001 (junction without refresh). A solid choice for distributed I/O architectures.
Manager’s Insight
This module reduces cabling complexity by merging data and power in one cable. It lowers installation costs and saves panel space. The 100‑mA current consumption is modest, leaving most of the 3‑A budget for actuators. The status LEDs help maintenance teams quickly identify power or communication issues. For machine builders, this module offers a future‑proof path to EtherCAT P networks.
Applicable Devices & Scenarios
- EtherCAT P networks: direct connection to sensors and actuators
- Distributed I/O: remote cabinets, conveyor systems, robotics
- Harsh environments: IP67 rated for washdown or outdoor use
- Machinery: packaging, printing, metalworking, woodworking
- System branches: use with EPP1332‑0001 or EPP1342‑0001
- Upgrade projects: replace conventional EtherCAT drops
Installation & Commissioning Guide
- Mounting: Fix the module directly on machine frames or panels (IP67).
- Connectors: Use M8 male/female sockets – screw‑type for secure connection.
- Wiring: Plug the EtherCAT P cable (ZK700x) into the IN port.
- Power: Connect 24 V DC to the M8 feed connector (US/UP).
- Downstream: Connect the OUT port to the next EtherCAT P device.
- LEDs: Check green LEDs for EtherCAT link and power status.
- No software setup: The module auto‑detects and forwards data.
Maintenance & Service Convenience
- IP67 housing protects against dust and water jets.
- LEDs simplify troubleshooting without opening the enclosure.
- M8 connectors allow quick cable replacement.
- No internal fuses to replace – overload protection via the power supply.
- Compact size (approx. 90 g) fits tight machine spaces.
Compatibility & System Integration
- Master: Any EtherCAT master (e.g., TwinCAT, other PLCs).
- Cables: Use BECKHOFF ZK700x‑xxxx‑0xxx for EtherCAT P.
- Junctions: EPP1332‑0001 (voltage refresh) and EPP1342‑0001 (non‑refresh).
- Power supply: 24 V DC (‑15 %/+20 %) via M8 connector.
- Data rate: 100 Mbit/s full‑duplex.
Certifications & Safety Standards
- CE – conforms to EU directives.
- UL – currently in preparation.
- IP 65/66/67 – protected against dust and water (EN 60529).
- EMC: EN 61000‑6‑2 (immunity) & EN 61000‑6‑4 (emission).
- Vibration/shock: EN 60068‑2‑6 / EN 60068‑2‑27.
Package Contents
- 1 × BECKHOFF EPP1321‑0060 module.
- No cables or connectors included (order separately).
- Quick reference leaflet (full manual available online).
Warranty & Shipping
- Warranty: 12 months against manufacturing defects.
- Shipping: 12‑24 hours dispatch (business days).
- Carriers: FedEx, UPS, DHL – worldwide express.
- Tracking number provided upon shipment.
Frequently Asked Questions (FAQ)
- What is the main function of the EPP1321‑0060?
It converts standard EtherCAT to EtherCAT P, providing data and power in one cable.
- How much current can it supply?
Up to 3 A per US and UP, total max. 3 A each.
- Does it support distributed clocks?
No, distributed clocks are not supported.
- Can I forward the power to another device?
Yes, the downstream M8 connector forwards US and UP optionally.
- Is this module suitable for outdoor use?
Yes, IP67 rating protects against rain and dust.
- What cables do I need?
Use ZK700x‑xxxx‑0xxx for EtherCAT P, or ZK1090/ZK2020 for power.
- Can I use this with non‑BECKHOFF masters?
Yes, any standard EtherCAT master works.
Experience‑Based Buying Guide
- Choose EPP1321‑0060 if you need a simple EtherCAT‑to‑EtherCAT P converter.
- For voltage refresh along long branches, add EPP1332‑0001.
- If no power boost is needed, select EPP1342‑0001 for passive junctions.
- Always verify total current draw of downstream devices ≤ 3 A per line.
- Use shielded M8 cables to maintain EMC performance.
- Order the matching power supply with 24 V DC, ±20 % tolerance.