Product details
ATV930D55N4C: 55 kW Variable Speed Drive from Schneider Electric
The ATV930D55N4C is a three-phase variable speed drive in the Altivar Process ATV930 series from Schneider Electric. It delivers 55 kW in normal duty and 45 kW in heavy duty. This wall-mounting unit runs on 380 to 480 V supply. It comes in an IP21/UL Type 1 enclosure. No braking unit is built in. You need an external braking unit for braking tasks. The drive fits pumps, fans, conveyors, and other industrial machines.
Technical Specifications
- Brand: Schneider Electric
- Model: ATV930D55N4C
- Series: Altivar Process ATV930
- Product type: Three-phase variable speed drive, wall-mounting, no built-in braking unit
- Motor power (ND): 55 kW (75 HP), 120% overload for 60 s
- Motor power (HD): 45 kW (60 HP), 150% overload for 60 s
- Supply voltage: 380 to 480 V three-phase, -15%/+10%, 50/60 Hz
- Output frequency: 0.1 to 599 Hz
- Switching frequency: 2.5 kHz nominal, with automatic derating above this level
- Continuous output current (ND): 106 A
- Transient output current (ND): 127.2 A for 60 s
- Continuous output current (HD): 88 A
- Transient output current (HD): 132 A for 60 s
- Input current (ND): 97.2 A at 380 V, 84.2 A at 480 V
- Input current (HD): 81.4 A at 380 V, 71.8 A at 480 V
- Apparent power: 70.0 kVA (ND) / 59.7 kVA (HD) at 380 V
- Motor control: Open and closed loop vector control for async, PM, and synchronous reluctance motors
- Short-circuit rating: 50 kA SCCR
- EMC filter: Category C3 integrated
- Safety: STO function, SIL3 / Cat. PL e
I/O and Communication
- Analog inputs: 3 total (2 voltage/current with probe input, 1 bipolar)
- Digital inputs: 8, 24 V DC, positive or negative logic
- Digital output: 1, configurable as pulse train output
- Analog outputs: 2, voltage or current
- Relay outputs: 3 (1 NO/NC + 2 NO)
- Safety inputs: 2 for STO
- Expansion: Up to 3 I/O modules
- Built-in ports: 1 Ethernet dual-port switch (RJ45), 1 Modbus serial port (RJ45)
- Protocols: EtherNet/IP, Modbus TCP, Modbus RTU
- Fieldbus slot: 1 slot for PROFINET, PROFIBUS DP V1, CANopen, DeviceNet, EtherCAT, or POWERLINK
- Cybersecurity: Achilles Level 2 certified
Environmental and Physical Data
- Operating temperature: -15 to +50 °C standard, derating up to 60 °C
- Storage temperature: -40 to +70 °C
- Humidity: 5 to 95%, non-condensing
- Altitude: No derating up to 1000 m, then 1% per 100 m up to 3000 m
- Environmental class: 3C3 / 3S3 / 3M3
- Protection rating: IP21 / UL Type 1
- Dimensions (H x W x D): 922 x 290 x 325.5 mm
- Weight: 56.500 kg (124.561 lb)
- Power dissipation: 1228 W (ND) / 919 W (HD) at nominal load
- Minimum air flow: 295 m³/h
Installation Guide
- Mount the drive vertically on a solid wall.
- Keep 100 mm clearance above and below the unit.
- Keep 10 mm clearance at the front.
- Tighten power terminals to 25 N·m.
- Use the correct cable size for 97.2 A input current.
- Connect an external braking unit when braking is needed.
- Check airflow at 295 m³/h for full load.
Setup and Maintenance
- Set motor data with the built-in keypad or software tools.
- Pick ND or HD rating to match your load profile.
- Use the dual Ethernet port for simple daisy-chain wiring.
- Check fans and heat sinks at each service interval.
- Read fault codes on the display for fast fixes.
- Update firmware through the Ethernet port.
Compatibility Notes
- Works with asynchronous, permanent magnet, and synchronous reluctance motors.
- Supports open-loop and closed-loop control with an encoder.
- Fits PROFINET, EtherCAT, CANopen, and other networks with one option module.
- Adds up to 3 I/O modules for more signals.
- Pairs with external braking units and resistors.
- Integrates with plant control through EtherNet/IP and Modbus TCP.
Certifications
- UL 508C and UL 61800-5-1
- EN/IEC 61800-3 (category C2/C3)
- EN/IEC 61800-5-1
- IEC 61508 and ISO 13849-1 for STO
- Achilles Level 2
- REACH and SEMI F47-0706
Package Contents
- 1 x ATV930D55N4C drive
- 1 x printed installation manual
- 1 x safety information sheet
- Terminal hardware as shipped by Schneider Electric
FAQ
- Does this drive include a brake chopper?
No. You must add an external braking unit for braking. - Can I run a 55 kW motor in heavy duty?
The heavy duty rating is 45 kW. Use normal duty for 55 kW loads. - What is the overload capacity?
Normal duty gives 120% for 60 s. Heavy duty gives 150% for 60 s. - How do I connect to a plant network?
Use the two RJ45 Ethernet ports for EtherNet/IP or Modbus TCP. - Is single-phase input possible?
No. This model needs three-phase 380 to 480 V supply. - What do field engineers check first on a tripped drive?
They read the fault code, then check motor load and cooling airflow. - How much space does the drive need around it?
Leave 100 mm above and below and 10 mm in front. - Can I add more I/O later?
Yes. The drive accepts up to 3 extra I/O modules. - What is the highest output frequency?
It reaches 599 Hz. - Does altitude affect the rating?
Yes. Above 1000 m, current drops 1% per 100 m. - What do experienced installers do before first start?
They verify terminal torque, motor data, and rotation direction. - How do maintenance teams cut downtime?
They log fault codes and clean heat sinks on a fixed schedule.