ATV930C11N4C Drive Overview

  • Brand: Schneider Electric
  • Series: Altivar Process ATV930
  • Model: ATV930C11N4C
  • Type: three-phase variable speed drive
  • Supply: 380…480 V
  • Mount: IP00 cabinet version
  • Rating: dual ND/HD
  • Braking: no built-in chopper. Add an external unit.

Power and Motor Data

  • ND power: 110 kW (150 HP)
  • ND overload: 120% for 60 s
  • HD power: 90 kW (125 HP)
  • HD overload: 150% for 60 s
    • Use HD for high peak loads
    • Use ND for normal pump and fan duty
  • Output frequency: 0.1…599 Hz
  • Switching frequency: 2.5 kHz nominal
    • Auto derating above nominal

Motor Control Modes

  • Asynchronous motor
    • Standard constant torque
    • Variable standard torque
    • Optimized torque mode
  • Synchronous PM motor
    • Open-loop vector control
    • Closed-loop vector control
  • Synchronous reluctance motor
    • Open-loop vector control
    • Closed-loop vector control

Safety and Braking

  • Safety: 1 STO function
  • Level: SIL3 / Cat. PL e
    • IEC 61508
    • ISO 13849-1
  • Braking: external unit required
    • No built-in brake chopper
    • External brake resistor: not applicable

I/O and Signals

  • Analog inputs: 3
    • 2 x 0…10 V or 0/4-20 mA
    • Probe input: PTC / PT100 / PT1000 / KTY84
    • 1 x 0…±10 V
  • Digital inputs: 8
    • 24 V DC
    • Positive or negative logic
  • Digital output: 1
    • Assignable as PTO
  • Analog outputs: 2
    • 0…10 V or 0/4-20 mA
  • Relay outputs: 3
    • 1 NO/NC
    • 2 NO
  • STO inputs: 2
  • I/O expansion: up to 3 modules

Network and Cybersecurity

  • Built-in Ethernet: dual-port switch (RJ45)
  • Built-in serial: Modbus (RJ45)
  • Protocols: EtherNet/IP and Modbus TCP
  • Serial: Modbus RTU/TCP
  • Option slot: 1 fieldbus module
    • PROFINET
    • PROFIBUS DP V1
    • CANopen
    • DeviceNet
    • EtherCAT
    • POWERLINK
  • Security: Achilles Level 2

Electrical Ratings

  • Supply: 380…480 V, -15%/+10%
  • Frequency: 50/60 Hz
  • ND input current
    • 201 A at 380 V
    • 165 A at 480 V
  • ND apparent power: 121.8 kVA at 380 V
  • ND output current In: 211 A max
  • ND transient current: 253 A for 60 s
  • HD input current
    • 170 A at 380 V
    • 143 A at 480 V
  • HD apparent power: 102.6 kVA at 380 V
  • HD output current In: 173 A max
  • HD transient current: 259.5 A for 60 s
  • SCCR: 50 kA max
  • EMC filter: C3 integrated

Environment and Durability

  • Environmental class: 3C3 / 3S3 / 3M3
  • Operating temperature: 0 to +40 °C
    • Derate from 40 to 50 °C
  • Storage temperature: -40 to +70 °C
  • Humidity: 5 to 95%, non-condensing
  • Altitude
    • 0…1000 m: no derating
    • 1000…3000 m: derate 1% per 100 m
  • Protection: IP00
    • Conformity kit for IP21 / UL Type 1

Physical and Installation

  • Power loss: 2638 W (ND) / 2087 W (HD)
  • Air flow: 600 m³/h minimum
  • Size (H×W×D): 852 x 320 x 393 mm
  • Weight: 82.000 kg
  • Terminal torque
    • Main: 27 N·m
    • Control: 13.5 N·m
  • Clearance
    • 250 mm above and below
    • 100 mm front
  • Frame: 6

Certifications

  • UL 508C
  • UL61800-5-1
  • EN/IEC 61800-3 (C2/C3)
  • EN/IEC 61800-5-1
  • IEC 61508
  • IEC 13849-1
  • Achilles Level 2
  • REACH
  • SEMI F47-0706

Best Fit Devices and Applications

  • Pumps
    • Water supply
    • Booster sets
  • Fans and blowers
    • HVAC air handling
    • Process ventilation
  • Compressors
    • Air systems
    • Process gas
  • Conveyors
    • Bulk material handling
    • Packaging lines
  • Mixers and agitators
    • Food and beverage
    • Chemical processing
  • Extruders and mills
    • Plastics
    • Mining
  • Hoists and cranes
    • Use HD rating and an external braking unit

FAQ

  • Q: Can this drive run a permanent magnet motor?
    A: Yes. It supports synchronous PM motors in open-loop and closed-loop vector control.
  • Q: What happens if the cabinet gets too hot?
    A: The drive works up to +40 °C. Above that, you must derate. From 40 to 50 °C, lower the load to stay safe.
  • Q: Do I need extra parts for a hoist application?
    A: Yes. Choose the HD rating and add an external braking unit. This gives 150% overload for 60 s and controlled stops.
  • Q: Can I read motor temperature directly?
    A: Yes. Two analog inputs accept PTC, PT100, PT1000, or KTY84 probes. This helps protect the motor.
  • Q: What is the first thing to check after wiring?
    A: Check main terminal torque at 27 N·m and control torque at 13.5 N·m. Then test the STO circuit before you run the motor.

Specifications

  • BrandAllen-Bradley
  • Part Number22A-B012F104
  • ConditionOriginal Brand New

Customers Reviews

There are no reviews yet.

Be the first to review “ATV930C11N4C Schneider Altivar Process Drive 110kW Cabinet Mount IP00”

Your email address will not be published. Required fields are marked *

Back to Top
Product has been added to your cart