Product details
ATV610C40N4 Variable Speed Drive for Pumps and Fans
The ATV610C40N4 from Schneider Electric is a robust variable speed drive. It belongs to the Easy Altivar 610 series. This model suits pumps and fans in building and industrial plants. It delivers 400 kW (600 HP) normal duty power. The drive runs on a 380…460 V three-phase supply. An integrated C3 EMC filter cuts wiring effort. A plain text display terminal VW3A1113 comes as standard. The unit ships with IP00 protection. An optional kit raises protection to IP21.
Engineers choose this drive for simple setup and tough environments. The fan is field-replaceable in under five minutes. Conformal coated boards resist dust and humidity. Modbus ports are built in for easy network access.
Technical Specifications
- Brand: Schneider Electric
- Model: ATV610C40N4
- Series: Easy Altivar 610
- Product type: Variable speed drive (AC frequency inverter)
- Motor compatibility: Three-phase asynchronous and synchronous motors, open loop
- Control modes: U/f Standard, 5-point, Quadratic, synchronous motor control, reluctance motor control
- Rated motor power: 400 kW (600 HP) normal duty; 355 kW (500 HP) heavy duty
- Frame size: 8B
- Supply voltage: 380…460 V AC, 50/60 Hz, three-phase
- Maximum input current: 697 A at 380 V; 583 A at 460 V
- Apparent power: 465 kVA at 460 V
- Short-circuit current rating: 50 kA prospective line Isc
- Continuous output current: 730 A normal duty
- Transient current: 803 A for 60 s normal duty
- Heavy duty rating: 355 kW, 616 A continuous, 924 A for 60 s
- Output frequency: 0.1…500 Hz
- Switching frequency: 2…8 kHz adjustable, 2.5 kHz nominal
- Overload duty: Normal duty 110% for 60 s or 120% for 20 s; heavy duty 150% for 60 s
- Analog inputs: 3, configurable 0…10 V / 0…20 mA
- Digital inputs: 6 at 24 V DC, two can act as pulse inputs
- Analog outputs: 2, configurable 0…10 V / 0…20 mA
- Relay outputs: 3, configurable logic
- Expansion slot: Slot A for I/O, relay or PROFIBUS DP V1 modules
- Built-in ports: 2 RJ45 Modbus serial-link ports
- Protocol: Modbus RTU over RS485
- Cooling: Fan cooled, field-replaceable in under five minutes
- Power dissipation: 7338 W total at nominal current
- Braking: Terminals PA/+ and PB for an external braking resistor
- Motor cable length: 150 m shielded, 200 m unshielded
- Input harmonics: Integrated DC choke; THDi below 10% only with optional passive filter
Operating Conditions and Protection
- Temperature range: -10…+40 °C without derating; up to +60 °C with derating
- Storage temperature: -25…+70 °C for frame sizes 7 and 8
- Humidity: 5…95%, non-condensing
- Altitude: Up to 1000 m without derating; 1000…3000 m with derating
- Protection rating: IP00, IP21 with optional kit
- Environmental class: 3C2 / 3S2 per IEC/EN 60721
- Mechanical class: 3M3
- Coating: Protective conformal coating on electronic cards
- Noise immunity: C3 EMC filter built in, supports stable operation near drives and cables
Installation Guide
- Mount the drive vertically, within plus or minus 10 degrees.
- Keep clearances of 200 mm top, 150 mm bottom and 10 mm front.
- Tighten power terminals to 41 N·m.
- Use the RJ45 field network port for process data.
- Use the HMI RJ45 port for the display terminal.
- Fit an output filter when motor cables exceed 50 m.
- Supply relay outputs from Overvoltage Category II. Add an isolation transformer if needed.
- Fit the IP21 kit in dusty or wet areas.
Setup and Maintenance
- The plain text terminal shows two lines on a white backlit LCD.
- Menus guide you through motor data and I/O setup.
- Diagnostic menus cover Modbus network and HMI ports.
- Replace the cooling fan in under five minutes without special tools.
- Keep air paths clear and check fans at each service visit.
- Check terminal torque after the first weeks of operation.
Compatibility
- Works with three-phase asynchronous motors.
- Works with synchronous motors and reluctance motors in open loop.
- Slot A takes the VW3A3203 extended I/O module.
- Slot A takes the VW3A3204 extended relay module.
- Slot A takes the VW3A3607 PROFIBUS DP V1 module.
- The HMI port supports the VW3A1113 terminal and Harmony or Magelis HMI units.
- Optional passive filters VW3A46xxx reduce THDi below 10%.
Certifications
- CE marking under the EMC directive
- CSA C22.2 No. 274 for Canada
- No UL listing is published in the official catalog
- Designed to IEC/EN 61800-5-1 for overvoltage category II relay supply
Packing List
- ATV610C40N4 drive unit
- Plain text display terminal VW3A1113
- Installation manual EAV64381
- IP21 conformity kit only when ordered as an option
- Braking resistor and output filter sold separately
FAQ
What motor power does this drive handle?
It handles 400 kW at normal duty and 355 kW at heavy duty.
Can I use it with a permanent magnet motor?
Yes. The control modes include open-loop synchronous motor control.
How do I reach THDi below 10%?
Add an external passive filter from the VW3A46xxx range. The DC choke alone does not reach this level.
What should I check when the display shows a Modbus fault?
Open the [Modbus network diag] menu. Check the A/B/SGND wiring and the slave address. Most faults come from loose shielding or wrong parity settings.
Why does the drive trip on overtemperature in summer?
Cabinet airflow is often too low. Clean the fan and verify clearances. Above 40 °C you must derate the output current.
How long does fan replacement take on site?
Under five minutes. No special tools are needed.
Is the keypad included?
Yes. The VW3A1113 plain text terminal ships with the drive.
What is the heaviest task this unit should not run?
Constant-torque loads above 355 kW. Use a heavy duty rated drive for those loads.