Product details
PSTX300-600-70 – Softstarter for Heavy-Duty Motors
- Product ID: 1SFA898114R7000
- ABB Type Designation: PSTX300-600-70
- Global Commercial Alias: PSTX300-600-70
- Rated Operational Current: 300 A (inline) / 515 A (inside delta)
- Operating Voltage: 208 … 600 V AC
- Control Supply: 100 … 250 V AC, 50/60 Hz
- Built‑in Bypass: saves energy and simplifies installation
- Communication: Modbus RTU + optional Anybus (Profinet, Ethernet/IP, etc.)
- Protection: electronic overload, phase loss, voltage imbalance, ground fault, and more
- Display: detachable full graphic, IP66 & outdoor rated
Product Description
- The PSTX300-600-70 is a three‑phase softstarter from ABB’s PSTX series.
- It controls motor start/stop via voltage or torque ramp.
- Rated for 300 A inline (up to 515 A inside delta).
- Ideal for pumps, fans, compressors, and conveyors.
- Built‑in bypass reduces heat and cuts energy waste.
- Includes torque control, current limit, kickstart, and pump cleaning.
- Supports jog, braking, stand‑still brake, and emergency/fire pump mode.
- Detachable IP66 graphic display for easy local monitoring.
- Fieldbus ready: Modbus RTU built‑in, plus optional Anybus modules.
- Complete solution for 30…1250 A inline or 52…2160 A inside delta.
Technical Specifications (MECE structured)
- Brand & Model
- Brand: ABB
- Model: PSTX300-600-70
- Product ID: 1SFA898114R7000
- Electrical Ratings
- Rated Voltage: 208 … 600 V AC
- Control Voltage: 100 … 250 V AC, 50/60 Hz
- Rated Current (inline): 300 A
- Rated Current (inside delta): 515 A
- Service Factor: 100%
- Starting Capacity: 4 × Ie for 10 s
- Performance & Control
- Ramp Time: 1 … 120 s
- Initial Voltage: 30 … 99%
- Current Limit: 1.5 … 7.5 × Ie
- Analog Output: 0…10 V, 0…20 mA, 4…20 mA
- Torque Control, Voltage Ramp, Soft Stop
- Environment & Mechanical
- Operating Temp: –25 … +60 °C
- Storage Temp: –40 … +70 °C
- Protection Degree: IP00 (main terminals)
- Display IP66 (outdoor rated)
- Dimensions: 258 × 470 × 279 mm
- Net Weight: 15.5 kg
- Protection & Diagnostics
- Overload, underload, phase loss, voltage imbalance
- Earth fault, locked rotor, over/under voltage
- PT‑100, PTC, and electronic overload
- Event log, real‑time clock, thyristor runtime
- Compliance & Certificates
- CE, CQC, DNV, CCC
- RoHS, REACH, TSCA compliant
- ETIM 9: EC000640
- eClass V11.0: 27370907
Installation & Commissioning
- Mounting: panel mount; main terminals are copper bars.
- Wiring: main circuit hole Ø10.2 mm; control circuit 2.5 mm².
- Torque: 25 N·m (main circuit).
- Quick Start Guide and Installation Manual included.
- Auto phase sequence detection simplifies hook‑up.
Maintenance & Service Convenience
- Detachable display for local diagnosis without opening panel.
- Event log and diagnostic LEDs (Ready, Run, Protection, Fault).
- Fieldbus failure & HMI failure alarms included.
- Thyristor runtime measurement predicts maintenance needs.
Compatibility & Communication
- Built‑in Modbus RTU (standard).
- Optional Anybus modules: Profinet, EtherNet/IP, Modbus TCP, EtherCAT, DeviceNet, CANopen, Profibus, BACnet.
- Hardwired I/O: Start/Stop/Reset + 3 programmable digital inputs.
- External adapter and fieldbus plug also supported.
- Compatible with all major PLC brands via optional gateways.
Applications & Suitable Devices
- Typical Motors: three‑phase induction motors from 30…1250 A inline.
- Pumps – soft start reduces water hammer.
- Fans – smooth acceleration lowers belt stress.
- Compressors – current limit protects mains.
- Conveyors – torque control for heavy loads.
- Emergency/Fire pump mode keeps critical systems running.
Expert Review
- “Built‑in bypass and torque control set this softstarter apart.”
- “The IP66 display is a lifesaver for outdoor or wash‑down areas.”
- “With 4×Ie starting capacity, it handles even high‑inertia loads.”
- “The broad communication options make it future‑proof for any plant.”
Manager‘s Insight
- “Reduces unscheduled downtime with advanced diagnostics and event log.”
- “Energy‑saving bypass and motor heating protection cut operational costs.”
- “Easy integration with existing Modbus networks saves engineering time.”
Frequently Asked Questions (FAQ)
- Question: What is the maximum motor power this softstarter can handle?
- Answer: Inline: 160 kW at 400 V; inside delta: 257 kW at 400 V.
- Question: Does it have built‑in overload protection?
- Answer: Yes, the electronic overload is integrated and fully adjustable.
- Question: Can I use it with a 600 V system?
- Answer: Yes, rated operational voltage is 208…600 V AC.
- Question: Is the display removable?
- Answer: Yes, it detaches for remote mounting and has IP66 rating.
- Question: What communication protocols are supported without extra modules?
- Answer: Modbus RTU is built‑in; others via optional Anybus modules.
- Question: How do I connect it inside delta?
- Answer: Use the built‑in switch for inside delta connection.
Experience‑based Tips & Selection Guide
- Tip 1: For high‑inertia fans, enable the kickstart function to break static friction.
- Tip 2: Use the pump cleaning routine to prevent clogging in dirty water pumps.
- Tip 3: Set the current limit to 3.5×Ie for most conveyor applications.
- Selection guide:
- Inline: choose PSTX300 for motors up to 160 kW (400 V).
- Inside delta: up to 257 kW (400 V) – use the built‑in delta switch.
- For 600 V: check the horsepower ratings (300 HP at 600 V).
- Consider ambient: operates from –25 °C to +60 °C; IP66 display for harsh environments.
Delivery & Warranty
- Shipping: 12‑24 hours dispatch via FedEx, UPS, or DHL.
- Warranty: 12 months against manufacturing defects.
- Package: 1 unit per box, dimensions 352×379×564 mm, gross weight 18.5 kg.