Product details
22A-A1P5F104 PowerFlex 4 AC Drive by Allen-Bradley
The 22A-A1P5F104 is a small, reliable AC drive from the Allen-Bradley PowerFlex 4 line. It takes 200–240V AC single-phase input. It gives 0.2 kW (0.25 HP) at 1.5 A. The flange mount saves panel space. An RS-485 DSI port and Modbus RTU come built in. It runs simple motors without extra cost or setup.
Core Specs at a Glance
- Brand: Allen-Bradley (Rockwell Automation)
- Model: 22A-A1P5F104
- Series: PowerFlex 4
- Type: AC adjustable-frequency drive
- Input: 200–240V AC, 1-phase, 50/60 Hz
- Input range: 180–265V AC
- Output power: 0.2 kW (0.25 HP)
- Output current: 1.5 A continuous
- Output voltage: 0–230V, three-phase
- Output frequency: 0–240 Hz, programmable
- Carrier frequency: 2–16 kHz, default 4 kHz
- Overload: 150% for 60 s, 200% for 3 s
- Efficiency: 97.5% typical
- Speed regulation: ±2% across 40:1 range
- Accel/decel: 0–600 s, 0.1 s steps
- Enclosure: Flange mount, IP20 open type
- Frame: A
- Cooling: convection, no fan
- Dimensions: 210.0 × 175.0 × 147.5 mm
- Weight: 3.372 kg
- Operating temp: -10 to +50 °C
- Storage temp: -40 to +85 °C
- Humidity: 0–95% non-condensing
- Altitude: 1000 m without derating
- Shock: 15 g, 11 ms
- Vibration: 1 g, 5–2000 Hz
- Sound: 50 dBA at 1 m
Catalog Suffix Tree
- 22A — PowerFlex 4 drive
- A — 240V AC, 1-phase input
- 1P5 — 1.5 A output, 0.2 kW / 0.25 HP
- F — flange mount, IP20 open type
- 1 — fixed keypad interface
- 0 — no integral EMC filter
- 4 — standard build
- 0 — no integral EMC filter
- 1 — fixed keypad interface
- F — flange mount, IP20 open type
- 1P5 — 1.5 A output, 0.2 kW / 0.25 HP
- A — 240V AC, 1-phase input
What It Is Good For
- Small conveyors and belt feeders
- Pumps and fans with light loads
- Door and gate operators
- Simple mixers and agitators
- Packaging indexers with basic speed control
- Hobby and workshop machines
- Retrofit jobs that need a tiny footprint
Installation Guide
- Cut the panel opening to 145 mm wide. Fit the flange through the cutout.
- Mount the drive vertically. No fan means free airflow matters.
- Wire 200–240V single-phase to L1 and L2. Ground the chassis.
- Connect the motor to T1, T2 and T3. Use a 10 A branch fuse.
- Add a brake resistor if you need fast stops. Use 60 Ω minimum.
- Fit the 22-JBAA kit for NEMA 1 protection.
- Use the L-type filter 22-RF010-AL for CE jobs.
- Keep motor cable short. 10 m max in most CE setups.
- Wire the RS-485 port with shielded twisted pair. Add terminators at the ends.
- Set node address, baud rate and RTU format before power-up.
Setup and Maintenance Ease
- Fixed keypad and LED display make setup quick.
- Set two accel and two decel times with simple parameters.
- Choose from Ramp, Coast, DC-Brake, Ramp-to-Hold or S Curve stops.
- Tune speed with the analog pot or a 0–10V / 4–20 mA signal.
- No fan means less dust and fewer parts to fail.
- Wipe the heatsink clean. Keep vents clear.
- Check RS-485 wiring if Modbus drops. Loose shields are a common cause.
Compatibility Notes
- Speaks Modbus RTU over RS-485 with function codes 03, 06 and 16.
- Supports up to 247 nodes. Add repeaters past 32 nodes.
- Works with the 1769-SM2 Compact I/O module.
- Uses the 22-XCOMM-DC-BASE kit for external network adapters.
- Accepts remote keypads 22-HIM-C2, 22-HIM-C2S and 22-HIM-A3.
- No encoder input and no closed-loop vector mode.
- No communication card slot. Use the RS-485 port or an external kit.
Certifications
- cULus: UL 508C and CSA C22.2 No. 14
- CE: EMC Directive 2014/30/EU and Low Voltage Directive 2014/35/EU
- Harmonics: meets EN 61000-3-2 without extra filters
- KC: registration KCC-REM-RAA-22A
- Ecodesign: meets IE2 efficiency class
- No STO: no functional safety rating on this model
Package Contents
- One 22A-A1P5F104 PowerFlex 4 AC drive, Frame A flange mount
- Fixed keypad and LED display, factory fitted
- Printed installation and safety sheets
Order separately: 22-JBAA IP30 kit, 22-RF010-AL line filter, brake resistor and RS-485 cable.
FAQ
- Can it run a motor with no encoder?
Yes. It is open-loop only. You set speed with a pot, a voltage signal or a network command. - Why does my drive stop when the panel gets hot?
The limit is 50 °C in open type. Fit the 22-JBAA kit and the limit drops to 40 °C. Improve airflow instead. - How short must the motor cable be for CE?
10 m with an L-type filter in restricted areas. Just 1 m in unrestricted areas with an S-type filter. - Does the flange mount fit a standard panel?
Yes. You need a 145 mm wide cutout. The body sits behind the plate and the heatsink stays outside. - What causes a Modbus timeout on this unit?
Wrong node address or a missing terminator. Check address A104 and baud rate A103 first. - Can I add a network card later?
No slot exists. Use the RS-485 port or an external 22-XCOMM-DC-BASE kit with an adapter. - Is a brake resistor required?
Only for hard stops or high inertia loads. Use 60 Ω or higher and a 5% duty cycle resistor.
















There are no reviews yet.