Product details
Produk-inleiding
- 22A-V2P3F104 is an AC adjustable-frequency drive from Allen-Bradley.
- Dit behoort aan die PowerFlex 4 family by Rockwell Automation.
- The drive takes 100…120V AC single-phase insette.
- It puts out 0.4 kW (0.5 HP) by 2.3A.
- The flange mount saves panel space.
- Housing is IP20 / NEMA UL Type Open.
- Geen EMC-filter is ingebou nie.
- 'n Integrale rem-IGBT is toegerus.
- A built-in RS-485 DSI port handles setup and network links.
Modelkodeboom
- 22A-V2P3F104
- 22A — PowerFlex 4 drive family
- V — 120V AC, 1-phase input
- 2P3 — 2.3 A-uitset, 0.4 kW / 0.5 HP
- F — Flange Mount, IP20, Type Open
- 1 — Fixed keypad interface
- 0 — Emission class: Not Filtered
- 4 — Type: Standard
- 0 — Emission class: Not Filtered
- 1 — Fixed keypad interface
- F — Flange Mount, IP20, Type Open
- 2P3 — 2.3 A-uitset, 0.4 kW / 0.5 HP
Sleutel data
- Merk: Allen-Bradley (Rockwell Automation)
- model: 22A-V2P3F104
- Reeks: PowerFlex 4
- tipe: WS-verstelbare frekwensie-aandrywer
- Raam grootte: A
- Beheermetode: PWM output with programmable carrier frequency, default 4.0 kHz
- Menslike koppelvlak: Vaste digitale sleutelbord met LED-skerm
- Afkoeling: Convection cooled for flange-mount drives
- Gewig: 3.434 kg per catalog data
- Afmetings (H × B × D): 8 350 × 2 600 × 3 250 mm oor die algemeen
- Depth is 92.8 mm drive body plus 54.7 mm heatsink.
Rygraderings
- Gegradeerde uitsetkrag: 0.4 kW (0.5 HP)
- Deurlopende uitsetstroom: Die 2.3
- Uitset spanning: 0…230V, driefase
- Uitset frekwensie: 0…240 Hz, programmeerbaar
- Draer frekwensie: 2…16 kHz, gegradeer teen 4 kHz
- Intermittent overload: 150% vir 60 s; 200% vir 3 s
- Doeltreffendheid: 97.5% tipies
- Spoedregulering: ±2% of base speed over a 40:1 range with slip compensation
- Frekwensie akkuraatheid: ±0.05% of set output frequency on digital input; 0.5% of max output frequency on analog input
- Versnel/vertrag: Two independent times, each 0…600 s in 0.1 s steps
- Stopmodusse: Ramp, Coast, DC-Brake, Ramp-to-Hold and S Curve
Beheer I/O
- Digitale insette: 3 dedicated plus 2 programmable
- Dedicated inputs are Stop, Start/Run FWD and Direction/Run REV.
- Input current is 6 mA.
- SRC mode: 18…24V DC = ON, 0…6V DC = OFF.
- SNK mode: 0…6V DC = ON, 18…24V DC = OFF.
- Analoog insette: 1, DIP-selectable 0…10V DC or 4…20 mA
- Analog input impedance is 100 kΩ in voltage mode and 250 Ω in current mode.
- Aflos uitset: 1 programmable Form C, 3.0 A resistive / 0.5 A inductive
- Enkodeerder terugvoer: Not supported on PowerFlex 4; no closed-loop vector mode is published
kommunikasie
- Ingeboude poort: 1 × RS-485 DSI, up to two peripherals per drive
- Modbus RTU: Function codes 03, 06 and 16
- Node adres: A104-reeks 1…247
- Baud koers: A103 range 1200…38400 bit/s, default 9600
- Format: A107 RTU 8-N-1
- Use RS-485 repeaters beyond 32 nodes.
- uitbreiding: No option-card slot; use external DSI kit 22-XCOMM-DC-BASE with adapters 22-COMM-C, 22-COMM-D, 22-COMM-E or 22-COMM-P
- Optional communications power supply: 20-XCOMM-AC-PS1
- Remote keypads: 22-HIM-C2, 22-HIM-C2S, 22-HIM-A3 with cables 22-HIM-H10 or 22-HIM-H30
Elektriese
- Spanning: 100…120V WS, 1-fase, ±10%
- Insetspanningreeks: 90…126V AC
- Invoerfrekwensie: 50 / 60 Hz
- Invoergraderings: 1.15 kVA, 9.0 A input current, 15 A branch fuse
- GS-bus oorspanningsuitskakeling: 405 V DC
- GS-bus onderspanningsuitskakeling: 210 V DC
- Kragdeurrit: 100 ms foutloos
- Logic control ride-through: 0.5 s minimum, 2 s tipies
- Oorstroom: 200% hardewarelimiet, 300% onmiddellike fout
- gerem: Integral brake IGBT; add an external resistor, minimum 60 Ω, catalog AK-R2-091P500 rated 5% duty
- Kragverlies: 40 W totaal, 22 W ekstern plus 18 W intern
Omgewing en Duursaamheid
- Temperatuur: -10…+50 °C for IP20 / Open Type
- IP30 / NEMA 1 / UL Type 1 version: -10…+40 °C
- Flange mount: heatsink -10…+40 °C, drive -10…+50 °C
- Stoor temperatuur: -40 ...+85 ° C
- Relatiewe humiditeit: 0…95% nie-kondenserend
- skok: 15 g peak for 11 ms, operating
- Vibrasie: 1 g peak, 5…2000 Hz, operating
- Klankdrukvlak: 50 dBA, Frame A, measured 1 m away
- Hoogte: 1000 m maksimum sonder afgradering
- atmosfeer: Must be free of volatile or corrosive gas, vapors and dust
Installasie Handleiding
- Mount the drive vertically in a clean, dry panel.
- Hou die hitteafvoer oop vir lugvloei.
- Use the flange opening to send heat outside the panel.
- Order kit 22-JBAA to reach IP30 / NEMA 1 protection.
- Fit an external EMC filter for CE compliance.
- Use filter 22-RF010-AL for this rating.
- Keep motor cable short: 10 m in restricted or second environment, 1 m in unrestricted distribution.
- Use 100 m cable with an external L-type filter.
- Wire branch protection with UL Class J, CC, T or BS88 fuses, or a Bulletin 140M/140MT motor protector.
- Connect the brake resistor only if dynamic braking is needed.
Opstelling en Onderhoudsgemak
- The fixed LED keypad makes local setup fast.
- Parameter A091 sets the PWM carrier frequency.
- Parameter A103 sets baud rate and A104 sets node address.
- Parameter A107 sets the RTU frame format.
- Parameter P037 selects the stop mode.
- Monitor d004 shows output voltage at T1, T2 and T3.
- Convection cooling means no fan to service on this mount style.
- RS-485 DSI port supports quick diagnostics and remote keypads.
Verenigbaarheidsnotas
- Runs standard three-phase AC induction motors up to 0.4 kW.
- Works with Modbus RTU masters over RS-485.
- Accepts 0…10V or 4…20 mA control signals.
- Accepts a 1…10 kΩ, 2 W minimum external potentiometer.
- Adds external DSI adapters for DeviceNet, ControlNet, EtherNet/IP or PROFIBUS.
- Works with 1769-SM2 Compact I/O module for multi-drive links.
- No encoder input, so skip closed-loop vector duties.
Certificaties
- cULus Gelys: UL 508C and CSA C22.2 No. 14
- CE: EMC Directive 2014/30/EU (EN 61800-3) and Low Voltage Directive 2014/35/EU (EN 61800-5-1)
- Harmoniese: Meets EN 61000-3-2 without extra parts
- KC: KCC-REM-RAA-22A
- Eko-ontwerp: Within EU 2019/1781 and UK SI 2021 No. 745 scope; meets IE2 class
- No Safe Torque Off function is published.
- No conformal coating class or pollution degree is assigned.
Pak lys
- 22A-V2P3F104 drive, 1 unit
- Fixed LED keypad, built in
- RS-485 DSI port, built in
- Integral brake IGBT, built in
- Gebruikershandleiding 22A-UM001L-AF-A verwysing
- No EMC filter in the box
- No brake resistor in the box
Beste Pas Toestelle en Toepassings
- Klein vervoerbande en indekseertafels
- Verpakkings- en etiketteermasjiene
- Small pumps and fans in light duty
- Machine tool feed and spindle helpers
- Food and beverage handling lines
- Material handling rollers and gates
- Retrofit jobs where panel depth is tight
- Modbus RTU networks with simple speed control
FAQ
- Can this drive take a 240V single-phase feed?
- No. This catalog code is set for 100…120V single-phase input.
- Pick a different voltage code for 200…240V or 380…480V.
- Is a braking resistor required for normal stops?
- No. Ramp and Coast stops work without one.
- Add a resistor only for fast stops or overhauling loads.
- How do I get NEMA 1 protection?
- Order the field kit 22-JBAA for Frame A.
- It raises the rating to IP30 / NEMA 1 / UL Type 1.
- From experience, why does a short motor cable still cause noise?
- Poor shield bonding is the common cause.
- Clamp the shield to the panel at both ends.
- Keep control and power wires in separate ducts.
- From experience, what trips this drive in summer panels?
- Heat builds up when the flange opening is blocked.
- Clear the cutout, check airflow, and respect the 50 °C limit.
- Also confirm the 40 W loss figure fits your cabinet budget.

















Daar is nog geen resensies nie.