Product details
MTL5043: Smart HART Signal Repeater for Explosive Zones
Powers HART transmitters in hazardous areas and drives two safe-zone loads with dual outputs.
Technical Specifications
Brand: MTL
Model: 5043
Suffix Structure:
MTL5043 ├── HART Support: Yes (Channel 1) ├── Input: 1 channel (0-24mA) ├── Outputs: │ ├── Ch1: Active (350Ω max) │ └── Ch2: Active/Passive (550Ω/1kΩ) └── Safety: Um=253V, Uo=28V
Performance Data
| Response Time | 500µs to 90% value |
| Accuracy | <20µA at 20°C |
| Temp. Stability | ±0.5µA/°C drift |
| HART Bandwidth | 400Hz–4kHz |
| Isolation | 250V between circuits |
| Ripple Noise | <125µA p-p |
| Power Range | 20-35V DC |
Unique Selling Points
- Flexible Outputs:
- Channel 1: 0-350Ω (standard) or 0-130Ω (HART mode)
- Channel 2: Active (550Ω) or passive sink (1kΩ/30V)
- Smart Diagnostics: HART data pass-through
- Low Heat: 1.7W max power dissipation
Wiring Guide
- Power: Terminals 14 (+) / 13 (-)
- Input: Terminals 2 (+) / 1 (-)
- Outputs:
- Ch1: 12 (+) / 11 (-) or 10 (+) for HART
- Ch2 Active: 9 (+) / 8 (-)
- Ch2 Passive: Terminal 7
Certifications & Safety
- ATEX/IECEx: Zone 0, IIC T4-T6
- UL/cUL: Class I Div.1 Group A
- Safety Limits:
- Uo=28V, Io=93mA
- Po=0.65W
Package Includes
- MTL5043 unit
- 12-month warranty
- Global shipping: FedEx/UPS/DHL
Expert FAQs
Q: Does terminal 10 support HART?
A: Yes – use with 220Ω resistor for HART devices.
Q: Max voltage on passive output?
A: 30V on terminal 7.
Q: Compatible with all HART devices?
A: Yes – ensures bidirectional communication.
Q: Power consumption at 24V?
A: 100mA with dual 20mA loads.
Q: Certification differences?
A: Baseefa 03ATEX0584 supports HART; BAS01ATEX7154 does not.