MTL5025 Intrinsic Safety Barrier: Reliable Hazardous Area Control for Switches & LEDs
Product Description
Control hazardous-area devices safely! The MTL5025 barrier lets you operate on/off equipment in Zone 0/Div.1 locations using safe-area switches. Works with intrinsically safe loads and simple devices like LEDs.
Technical Specifications
- Brand/Model: MTL5025 Standard Series
- Input Voltage: 20-35V DC
- Output Current: 45mA max
- Output Voltage: 8.6V-24V
- Power Consumption: 90mA@24V
- Temperature Range: -20°C to +60°C
- Safety Ratings:
- ATEX/IECEx Zone 0, IIC, T4-T6
- UL Division 1, Group A
- Um = 250V AC/DC
- Terminal Functions:
- 1: Output (–) | 2: Output (+)
- 3: Earth leakage | 11: Supply (–)
- 12: Supply (+)
Compatibility
- Certified IS low-power loads
- Non-storing simple apparatus (LEDs)
- Switch controls from safe areas
Packaging & Support
- Warranty: 12 months
- Shipping: FedEx, UPS, DHL
- Contents: Barrier unit, datasheet
Frequently Asked Questions
- Q: Can this drive solenoids?
A: Only certified IS loads under 45mA - Q: Is external grounding needed?
A: Use Terminal 3 for earth leakage detection - Q: Temperature limits?
A: Standard range: -20°C to +60°C
There are no reviews yet.