Product details

Key Features for TC-FIA121:

  • Inputs: 12 single-ended, non-isolated channels
  • Input Configurations:
    • 4-20mA or 0-20mA for current
    • ±10V or 0-10V for voltage
  • Conversion Rate: 8.0 ms across all channels
  • Data Format: 16-bit 2’s complement
  • Resolution:
    • Voltage: 320µV per count
    • Current: 0.641µA per count
  • Thermal Dissipation: 4.1 BTU/hr at 31.2V dc
  • Indicators: Green/red power/status indicator for easy monitoring
  • No Calibration Required: Plug-and-play setup

Technical Specifications:

  • Input Impedance:
    • Voltage: >1 megohm
    • Current: <100 ohms
  • Isolation Voltage: 50V continuous, tested at 850V dc for 60 seconds
  • Overload Protection: 30V or 32mA continuous (1 channel at a time)
  • Accuracy:
    • Voltage/Current Terminal: 0.10% Full Scale at 25°C
    • Drift: 0.004% Full Scale/°C for both terminals
  • Flexbus Current: 80mA at 5V dc
  • Power Dissipation: 1.2W maximum at 31.2V dc

Environmental Conditions:

  • Operating Temperature: -20 to 60°C (-4 to 140°F)
  • Storage Temperature: -40 to 85°C (-40 to 185°F)
  • Relative Humidity: 5 to 95% non-condensing
  • Shock Resistance:
    • Operating: 30g
    • Non-operating: 50g
  • Vibration Resistance: 5g at 10-500Hz

Dimensions:

  • Size: 94mm x 94mm x 53.3mm (3.7in x 3.7in x 2.1in)

Applications:

  • Industrial Automation: Ideal for process control, data acquisition, and control systems requiring precise voltage/current input measurements.
  • Power Monitoring: Used in systems that demand high accuracy for voltage and current readings.
  • OEM Equipment: Suitable for integration into custom equipment and systems.

FAQ:

  1. What is the input range for voltage?
    • The module supports ±10V or 0-10V voltage inputs, configurable by the user.
  2. How many channels does this module support?
    • It has 12 single-ended, non-isolated input channels.
  3. Is calibration required?
    • No, the TC-FIA121 does not require calibration and is ready for use out of the box.
  4. What is the maximum input current?
    • The module supports a maximum input of 32mA on a per-channel basis.
  5. What is the isolation voltage of this module?
    • The module features 50V continuous isolation voltage, with testing up to 850V dc.