Product details
Precision input: CC-PAIL51
The Honeywell CC-PAIL51 is a Low Level Analog Output module. It reads thermocouples and RTDs with high accuracy. Part of the I/O family, it connects to CC-TAIL51 9″ IOTA. Each channel is fully isolated. This module works in extreme temperatures. Ideal for critical process control.
Model structure explained
- CC – Series: Honeywell Control Core
- PAIL – Function: Low Level Analog Input
- 51 – Type: 16-point module, works with CC-TAIL51 IOTA
- PAIL – Function: Low Level Analog Input
Technical highlights
- Input type: Thermocouple or RTD – configurable per channel.
- Isolation: Full channel-to-channel and channel-to-power isolation.
- Scan rate: 1 second per channel – steady and reliable.
- Bandwidth: 0 to 4.7 Hz (-3 dB) – filters noise well.
- TC range: -20 to +100 millivolts nominal input.
- RTD excitation: 1 milliamp current source.
- Gain error: Only 0.050% full scale maximum.
- Temp stability: ±20 ppm/°C max for TC and RTD.
- CMRR: 120 dB min at 50/60 Hz – rejects interference.
- Open detect: 1000 Ω no-trip, 1500 Ω guaranteed trip.
Operating conditions
- Operating temp: -40°C to +70°C – tough industrial use.
- Storage temp: -40°C to +85°C – survives harsh storage.
- CMV tolerance: ±250 VDC or VAC RMS – strong protection.
- Line frequency: Fixed 50 Hz or 60 Hz selection.
- Cold junction: -20°C to +60°C range, ±0.5°C accuracy.
Supported sensor types
- RTD types:
- Pt 100 DIN: -180 to +800°C
- Pt 100 JIS: -180 to +650°C
- Ni 120 ED #7: -45 to +315°C
- Cu 10 SEER: -20 to +250°C
- Cu 50 SEER: -50 to +150°C
- Thermocouple types (ANSI):
- J: -200 to +1200°C
- K: -100 to +1370°C
- E: -200 to +1000°C
- T: -230 to +400°C
- B: +100 to +1820°C
- S: 0 to +1700°C
- R: 0 to +1700°C
- Millivolt input: -20 to +100 mV range.
Five professional FAQs
- Q1: What IOTA base does this module need?A1: It mates with CC-TAIL51 9-inch IOTA. The IOTA provides backplane connections and power distribution.
- Q2: Can I mix TC and RTD types on one module?A2: Yes, each of the 16 channels is configurable independently. You can mix thermocouples and RTDs freely.
- Q3: How does cold junction compensation work?A3: Built-in CJC measures terminal temp from -20°C to +60°C. Accuracy is ±0.5°C typical. No extra parts needed.
- Q4: What is the maximum RTD lead resistance allowed?A4: Maximum lead resistance is 15 Ω per lead. Higher resistance may affect accuracy. Use appropriate wire gauge.
- Q5: How fast do you ship this module?A5: We ship same day via FedEx, UPS, or DHL. Express delivery takes 2-4 business days. Tracking provided.
Selection guidance
- Choose CC-PAIL51 for 16-channel TC/RTD mixing.
- Needs isolation? Each channel is fully isolated from others.
- Works great with Honeywell C300 or similar controllers.
- 12-month warranty covers defects. Extended options available.
- Perfect for refineries, power plants, and chemical processes.
Contact information
- Technical questions: sales@powergearx.com
- Quick WhatsApp support: +86 18030005825
- Product details: Original Source
Copyright © 2026 Powergear X Automation Limited. All rights reserved.